Daikin VRV III RXYQ_PTJU Engineering Data page 4

3 phase, 208-230v 60hz
Table of Contents

Advertisement

EDUS39-802A-R1_a
Model Name
Model (Independent Unit)
Power Supply
1 Cooling Capacity
2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor Output×Number
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
High Pressure Equalizer
Pipe
Connecting
Pipes
Gas Pipe
Low Pressure Gas Pipe
Mass
4 Sound Level (Reference Value)
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 80°FDB or 67°FWB / outdoor temp. : 95°FDB / Equivalent piping length : 25 ft (7.5 m), level difference : 0 ft.
2 Indoor temp. : 70°FDB / outdoor temp. : 47°FDB or 43°FWB / Equivalent piping length : 25 ft (7.5 m), level difference : 0 ft.
3 BHFP22P100U is necessary for the connection.
Concerning about the piping connection for each outdoor unit to the main line as shown above, use REFNET.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
RXYQ-P Heat Pump (208-230V)
RXYQ144PTJU
3 Phase 60Hz 208V-230V
Btu / h
144,000
Btu / h
162,000
Ivory White (5Y7.5/1)
66-1/8 × 36-5/8 × 30-1/8"
in (mm)
(1680 x 1300.2 x 765 mm)
Cross Fin Coil
Hermetically Sealed Scroll Type
3
m
/h
16.90+16.90
r.p.m
7980, 7980
kW
3.8+3.8
Direct on Line
Propellor Fan
kW
0.75 × 2
cfm
8,299
Direct Drive
φ1/2" (12.7 mm) C1220T
in (mm)
(Brazing Connection)
in (mm)
φ 1-1/8" (28.6 mm) C1220T
in (mm)
(Brazing Connection)
in (mm)
Lbs
747 lbs (338.8 kg)
(kg)
dBA
61
High Pressure Switch,
Fan Driver Overload Protector,
Overcurrent Relay,
Inverter Overload Protector
Deicer
%
10~100
R-410A
Lbs
24.5
Electronic Expansion Valve
Installation Manual,
Operation Manual,
Connection Pipes, Clamps
4D058608
RXYQ168PTJU
RXYQ72PTJU
RXYQ96PTJU
3 Phase 60Hz 208V-230V
168,000
189,000
Ivory White (5Y7.5/1)
66-1/8 × 36-5/8 × 30-1/8"
(1680 x 930 x 765 mm) +
66-1/8 × 36-5/8 × 30-1/8"
(1680 x 930 x 765 mm)
Cross Fin Coil
Hermetically Sealed Scroll Type
16.90 + (10.53+13.34)
7980, (2900, 6300)
(4.7) × 1 + (2.2+4.5) × 1
Soft Start
Propellor Fan
(0.75) × 1 + (0.75) × 1
6,530+6,530
Direct Drive
φ 5/8" (15.9mm) C1220T
3
(Brazing Connection)
φ 3/4" (19.1 mm) C1220T
(Brazing Connection)
φ 1-1/8" (28.6 mm) C1220T
3
(Brazing Connection)
φ 3/4" (19.1 mm) C1220T
(Brazing Connection)
560+560 lbs (254 + 254 kg)
High Pressure Switch,
Fan Driver Overload Protector,
Overcurrent Relay,
Inverter Overload Protector
Deicer
9~100
R-410A
18.1+19.8
Electronic Expansion Valve
Installation Manual,
Operation Manual,
Connection Pipes, Clamps
4D060126
Specifications
RXYQ192PTJU
RXYQ72PTJU
RXYQ120PTJU
3 Phase 60Hz 208V-230V
192,000
216,000
Ivory White (5Y7.5/1)
66-1/8 × 36-5/8 × 30-1/8"
(1680 x 930 x 765 mm) +
66-1/8 × 36-5/8 × 30-1/8"
(1680 x 930 x 765 mm)
Cross Fin Coil
Hermetically Sealed Scroll Type
16.90 + (10.53+13.34)
7980, (2900, 6300)
(4.7) × 1 + (3.5+4.5) × 1
Soft Start
Propellor Fan
(0.75) × 1 + (0.75) × 1
6,530+7,060
Direct Drive
φ 5/8" (15.9mm) C1220T
3
(Brazing Connection)
φ 3/4" (19.1 mm) C1220T
(Brazing Connection)
φ 1-1/8" (28.6 mm) C1220T
3
(Brazing Connection)
φ 3/4" (19.1 mm) C1220T
(Brazing Connection)
560+560 lbs (254 + 254 kg)
High Pressure Switch,
Fan Driver Overload Protector,
Overcurrent Relay,
Inverter Overload Protector
Deicer
7~100
R-410A
18.1+20.1
Electronic Expansion Valve
Installation Manual,
Operation Manual,
Connection Pipes, Clamps
4D060127
3