Installing Power Distribution Unit (2U) - Fujitsu ETERNUS DX80 S2 User's Manual & Installation Instructions

Disk storage system
Hide thumbs Also See for ETERNUS DX80 S2:
Table of Contents

Advertisement

Chapter 3 Rack Installation
3.1 Installing Power Distribution Unit (For Regions other than EMEA&I)
3.1.2

Installing Power Distribution Unit (2U)

This section describes how to install the Power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 2U, Max 6
enclosures connection) or Power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 2U, Max 8 enclosures
connection) in a rack.
This section explains the installation procedure for Power distribution unit for DX80 S2/DX90 S2 (AC200-
240V, 2U, Max 6 enclosures connection). This procedure can also be applied for Power distribution unit for
DX80 S2/DX90 S2 (AC200-240V, 2U, Max 8 enclosures connection).
Procedure
1
Attach the M5 cage nuts to the rear rack pillar.
Attachment positions
On either side, insert eight M5 cage nuts in the 1st, 3rd, 4th, and 6th holes above the power
distribution unit base line.
M5 cage nut
6th position
4th position
3rd position
1st position
Attachment procedure
Clip the M5 cage nut tabs into the desired hole from the inside.
ETERNUS DX80 S2/DX90 S2 Disk storage system User's Guide -Installation-
(Rear rack pillars)
[Left]
2U
1U
Power distribution unit
1U
Power distribution unit
Base line of
power distribution unit
Side view
M5 cage nut
Rack pillar (square)
Copyright 2013 FUJITSU LIMITED
M5 cage nut
[Right]
6th position
4th position
3rd position
1st position
50
P3AM-4832-07ENZ0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eternus dx90 s2

Table of Contents