Troubleshooting Using The Embedded Management System - GE MDS entraNET 900 Technical Manual

900 mhz and 2400 mhz extended range ip networking transceivers
Table of Contents

Advertisement

168
Table 7-1. Symptom-Based Troubleshooting Using LEDs
Symptom
PWR LED does not
turn on.
LINK LED does not
turn on.
PWR LED is
blinking.
LAN/ETH LED
does not turn on.
COM1 or COM2
LED does not show
traffic.
Table 7-2
shows the proper type of Ethernet cable to use with the radio
when connecting to external devices.
Table 7-2. Proper Ethernet Cable Type
Radio Type
AP
AP
Remote
Remote
7.1.2 Troubleshooting Using the Embedded
Management System
If following the suggestions in
there are additional tools and techniques that you can use. The
Embedded Management System is a good source of information that
MDS entraNET Technical Manual
Possible Cause and Resolution
a. The voltage is too low, or is the wrong polarity. Check for
the proper supply voltage at the power connector
(6–30 Vdc). See
Figure 2-4 on Page 20
b. This is a transient condition. Cycle the power and wait
approximately 30 sec for the radio to restart. Recheck for
normal operation.
a. The Remote network address does not match the desired
AP. Verify that the system has a unique network address.
b. The Remote is not yet associated with a transceiver having
the same network address. Use the RADIO command to
check the status of the process of associating the radio
with the AP.
c. Poor antenna system. Check the antenna, feedline, and
connectors. Reflected power should be less than 10% of
the forward power reading (SWR 2:1 or lower). Also, check
for the proper heading of the directional antennas as
described in
Aiming Directive Antennas for Maximum RSSI
on Page 162.
The radio is reporting an alarm condition. View the current
alarms and the Event Log. Correct the problem if possible
(see "Using Logged Operation Events" on Page
Blinking continues until the source of the alarm is corrected
(for example, a valid IP address is entered, and so on).
a. Verify that the Ethernet cable is connected at both ends.
b. Verify that the proper type of Ethernet cable
(straight-through or crossover) is used. See
the proper cable type.
Check the configuration of the COM port and the remote serial
gateway settings.
Connected Device
Hub or network switch
PC
PC
Hub or network switch
Table 7-1
does not resolve the problem,
for polarity details.
172).
Table 7-2
for
Cable Type Required
Straight-through
Crossover
Straight-through
Select for the external
device port
05-4055A01, Rev. E