Download Print this page

Specifications; Ordering Information - Honeywell R7795A Manual

Flame safeguard primary controls

Advertisement

R7795A,B,C,D
SPECIFICATIONS • ORDERING INFORMATION
Model
R7795A,C
R7795B,D
a
Order flame rod separately.
b
Use Honeywell part no. 38316 Photocell only.
Flame
Detection
R7795
R7795A
UV
R7795B
Rectification
R7795C
UV
R7795D
Rectification
a
Field selectable:
10 sec with the orange jumper wire unclipped.
4 sec with the orange jumper wire clipped.
b
Field selectable:
Recycle with the yellow jumper wire unclipped.
Lockout with the yellow jumper wire clipped.
When purchasing replacement and modernization products from your TRADELINE® wholesaler or your distributor, refer to the
TRADELINE Catalog or price sheets for complete ordering number, or specify—
1. Order number, TRADELINE, if desired.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Home and Building Control Sales Office (check white pages of phone directory).
2. Home and Building Control Customer Satisfaction
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International
Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany,
Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
TABLE 1—FLAME DETECTION SYSTEMS.
Flame Detection
Amplifier Type
Ultraviolet (purple)
Rectification (Green)
TABLE 2—R7795 MODELS AVAILABLE.
Amplifier
Type
Color
Purple
Green
Purple
Green
Fuel
Gas, oil
UV (Minipeeper)
Gas
Rectifying flame rods
Oil
Rectifying photo cells
Gas, oil, coal
UV (Purple Peeper)
Flame Establishing
Period (sec)
a
Pilot
Main
Intermittent
Intermittent
Pilot
10/4
10
Interrupted
Seconds

Ordering Information

2

Specifications

Applicable Flame Detectors
Type
C7027, C7035, C7044
Holders:
C7007, C7011
Complete Assy:
C7005, C7008,
C7009, Q179
b
C7003, C7010,
C7013, C7014
C7012A,C
Flame Failure
Nominal
Device
Response (sec)
Reaction
3
Recycle
or Lockout
Models
a
C7004,
Run/Test
b
Switch
No
Yes

Hide quick links:

Advertisement

loading

This manual is also suitable for:

R7795dR7795bR7795c