ELECTRIC,
REQUIREMENW$
it is your responsibility:
[] To contact a qualified electrical installer.
[] To be sure that the electrical connection is adequate and in
conformance
with the National Electrical Code, ANSI/NFPA 70
- latest edition and all local codes and ordinances.
The National Electrical Code requires a 4-wire power supply
connection for homes built after 1996, dryer circuits involved in
remodeling after 1996, and all mobile home installations.
A copy of the above code standards can be obtained from:
National Fire Protection Association,
One Batterymarch
Park,
Quincy, MA 02269.
[] To supply the required 3 or 4 wire, single phase, 120/240
volt, 60 Hz, AC only electrical supply (or 3 or 4 wire, 120/208
volt electrical supply, if specified
on the serial/rating
plate)
on a separate 30-amp circuit, fused on both sides of the line.
Connect to an individual branch circuit. Do not have a fuse in
the neutral or grounding circuit.
[] Do not use an extension cord.
[] If codes permit and a separate ground wire is used, it is
recommended
that a qualified electrician determine that the
ground path is adequate.
Electrical
Connection
To properly install your dryer, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
[] This dryer is manufactured
ready to install with a 3-wire
electrical supply connection. The neutral ground conductor
is permanently connected to the neutral conductor
(white wire)
within the dryer. If the dryer is installed with a 4-wire electrical
supply connection,
the neutral ground conductor
must be
removed from the external ground connector
(green screw),
and secured under the neutral terminal (center or white wire)
of the terminal block. When the neutral ground conductor
is
secured under the neutral terminal (center or white wire) of the
terminal block, the dryer cabinet is isolated from the neutral
conductor.
[] If local codes do not permit the connection of a neutral
ground wire to the neutral wire, see "Optional 3-wire
connection"
section.
[] A 4-wire power supply connection must be used when the
appliance is installed in a location where grounding through
the neutral conductor
is prohibited.
Grounding through the
neutral is prohibited for (1) new branch-circuit
installations,
(2) mobile homes, (3) recreational vehicles, and (4) areas
where local codes prohibit grounding through the neutral
conductors.
if using a power
supply
cord:
Use a UL listed power supply cord kit marked for use with
clothes dryers. The kit should contain:
[] A UL listed 30-amp power supply cord, rated 120/240 volt
minimum. The cord should be type SRD or SRDT and be
at least 4 ft. (1.22 m) long. The wires that connect to
the dryer must end in ring terminals or spade terminals
with upturned ends.
[] A UL listed strain relief.