Electrical Requirements - Frigidaire FRQE7000LW0 Installation Manual

Hide thumbs Also See for FRQE7000LW0:
Table of Contents

Advertisement

Available languages

Available languages

Electrical requirements
for electric dryer
CIRCUIT - Individual 30 amp. branch circuit fused with 30 amp. time delay fuses or circuit breakers. Use separately
fused circuits for washer and dryer. DO NOT operate a washer and a dryer on the same circuit.
POWER SUPPLY - 3-wire or 4-wire, 240 volt, single phase, 60 Hz, Alternating Current.
This dryer is internally grounded to neutral unless it was manufactured for sale in Canada.
Only a 4-conductor cord shall be used when the appliance is installed in a location where grounding through
the neutral conductor is prohibited. Grounding through the neutral link is prohibited for: (1) new branch circuit
installations, (2) mobile homes, (3) recreational vehicles, and (4) areas where local codes do not permit grounding
OUTLET RECEPTACLE- NEMA 10-30R or NEMA 14-30R receptacle to be located so the power supply cord is accessible
when the dryer is in the installed position.
GROUNDING CONNECTION - See "Grounding requirements" in Electrical Installation section.
3-WIRE POWER SUPPLYCORD KIT (not supplied)
3-wire
receptacle
(NEMA type 10=30R)
The dryer MUST employ a 3-conductor power
supply cord NENA 10-30 type SRDT rated at 240
volt AC minimum, 30 amp, with 3 open end spade
lug connectors with upturned ends or closed
loop connectors and marked for use with clothes
dryers. For 3-wire cord connection instructions see
ELECTRICAL CONNECTIONS FOR A 3-WIRE SYSTEM.
4-WIRE POWER SUPPLYCORD KIT (not supplied)
4-wire receptacle
(NEMA type 14=30R)
The dryer MUST employ a 4-conductor power supply
cord NEMA 14-30 type SRDT or ST (as required) rated
at 240 volt AC minimum, 30 amp, with 4 open end
spade lug connectors with upturned ends or closed
loop connectors and marked for use with clothes
dryers. For 4-wire cord connection instructions see
ELECTRICAL CONNECTIONS FOR A 4-WIRE SYSTEM.
Dryers manufactured for sale in Canada have factory-
installed, 4:w! re power Su pply €ord (NEMA 14:30R): .............................