Gas Conversions - Kenmore 66575169300 Installation Instructions Manual

30" freestanding sealed burner gas range
Table of Contents

Advertisement

Explosion Hazard
Use a new AGA or CSA approved gas supply
line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to LP, have a qualified person
make sure gas pressure does not exceed 14"
water column.
Examples of a qualified person include:
licensed heating personnel;
authorized gas company personnel; and,
authorized service personnel.
Failure to follow these instructions can result
in death, explosion, or fire.
Observe all governing codesand ordinances.
This installation must conform with all local codesand
ordinances.In the absence of local codes, installation
must conform with American National Standard,
National Fuel Gas Code ANSI Z223.1 -- latest edition*.
Input ratings shown on the model/serial rating plate are
for elevations up to 2,000feet. For assistance when
installing the range at higher elevations, contact your
local Sears Service Center.
Type of gas: This range is design-certified by the
American Gas Association (A.G.A.)for use with Natural
gas or, after proper conversion, for use with
L. P. gas. This range is factory set for use with Natural
gas. Gas conversion instructions are provided. The
model/serial rating plate located on the frame behind
the storage drawer has information on the types of gas
that can be used. If the types of gas listed do not
include the type of gas available, check with the local
gas supplier.
Peligro de Explosibn
Use una linea de suministro de gas nueva aprobada
por AGA o CSA.
Instale una v_lvula de cierre.
Apdete firmamente todas las conexiones de gas.
Si estb conectada a gas de P.L., haga que una
persona calificada asegure que la presibn de gas
no exceda de una columna de agua de 14".
Ejemplos de personas califlcadas son miembros
del personal de calefaccibn con licencia, personal
autorizado de la compa_ia de gas y personal de
servicio autorizado.
No seguir estas instrucciones puede ocasionar la
muerte, una explosibn o un incendio.
Observe todos los cbdigos y reglamentos
vigentes.
Esta instalacion debe cumplir con todos los cbdigos y
reglamentos
locales. A falta de c6digos locales, la
instalaci6n debe cumplir con American
National
Standard, National Fuel Gas Code ANSI Z223.1--61tima
edici6n *.
Las clasificaciones
de entrada
que se indican en la
placa de modelo/serie
son para elevaciones
de hasta
2,000 pies sobre el nivel del mar. Para asistencia
cuando instale la cocina en lugares
con mayor
altitud,
contacte a su Centro
de Servicio Sears.
Tipo de gas: El disefio
de esta cocina ha sido
certificado
por la American
Gas Association
(A.G.A.)
para uso con gas Natural o, despu_s
de la debida
conversi6n,
para uso con gas de P.L. Esta cocina ha
sido ajustada en la fbbrica para uso con gas Natural.
Las instrucciones
de conversi6n
de gas aparecen.
La
placa de modelo/serie
ubicada en el marco
detr_s del
caj6n de almacenamiento,
contiene informaci6n
sobre el tipo de gas que se puede usar. Si los tipos de
gas indicados no incluyen el tipo de gas disponible,
contacte a la compaflia
de gas de su Iocalidad.
10
manual
shutoff valve"open"
position
valvula de cierra manual on la \
posicibn "abierta"
_
to range
__,r,_'_JJl_\
%.
gas
s.pp,,,__
,,--,.27,,,,o
de gas
Conversion mustbe done by a qualified service
technician.
Gas supply line: Provide a gas supply line of 3/4" rigid
pipe to the range location. With L.P. gas, piping or
tubing size can be 1/2" minimum. A smaller size pipe
on longer runs may result in insufficient gas supply.
Usually, L.P. gas suppliers determine the size and
materials used in the system.
Pipe-joint compounds made for use with LP. gas must
be used on pipe threads only.
Flexible metal appliance connector: If local codes
permit, a new A.G.A. design-certified, 1/2" or 3/4" I.D.,
flexible metal appliance connector is recommended
for connecting range to the gas supply line. A 1/2"
male pipe thread nipple is needed for connection to
the female pipe threads of the inlet to the appliance
pressure regulator. Do Not kink or damage the flexible
metal tubing when moving the range.
Rigid pipe connection: Requires a combination of pipe
fittings to obtain an in-line connection to the range. All
strains must be removed from the supply and fuel
lines so range will be level and in line.
Shutoff valve: The supply line must be equipped with
a manual shutoff valve. This valve should be located in
the same room asthe range and should be in a
location that allows ease of opening and closing. The
valve is for turning on or shutting off gas to the range.
Do Not block accessto shutoff valve.
Pressure regulator: The gas pressure regulator
supplied with this range must be used. The inlet
pressure to the regulator should be as follows for
proper operation:
NATURAL GAS:
Minimum pressure: 5 inchesWCP
Maximum pressure: 14 inchesWCP
LP. GAS:
Minimum pressure: 11 inches WCP
Maximum pressure: 14 inchesWCP
Contact local gas supplier if you are not sure about the
inlet pressure.
La conversion
debe ser hecha por un tecnico de
servicio calificado.
Linea de suministro
de gas: Instale
una linea de
suministro
de gas de tubo
rigido
de 3/4" hasta la
cocina.
Para el gas de P.L., el tubo
debe medir
un
mlnimo
de 1/2". Un tubo
m&s pequeflo
para
recorridos
m_s largos,
podrla
ocasionar
un
suministro
de gas insuficiente.
Usualmente,
las
compafiia
proveedoras
de gas de P.L. determinan
las dimensiones
y los materiales
usados en el
sistema.
Los compuestos
para juntas de tubo disefiados
para uso con gas de P.L. deben usarse
L_nicamente
en las roscas del tubo.
Conector
de electrodomdsticos
de metal flexible: Si
los c6digos
locales Io permiten,
se recomienda
usar
un conector de electrodomesticos
de metal
flexible
con dibmetro
interno de 1/2" 6 3/4", con disefio
certificado
por la A.G.A.,
para conectar
la cocina a
la linea de suministro
de gas. Se necesita
una
boquilla acopladora
macho de 1/2" para la conexi6n
a la rosca de tuberia hembra del regulador
de
presi6n. AI mover la cocina, no enrosque
ni dafie el
tubo de metal flexible.
Conexion
con tubo rigido: Requiere
de una
combinaci6n
de accesorios para tubos para Iograr
una conexi6n
en la linea a la cocina. Deben
eliminarse
las deformaciones
de las lineas de
suministro
y combustible
para que la cocina estb
nivelada
yen
linea.
Valvula
de cierre: La linea de suministro
debe estar
equipada
con una vblvula de cierre manual.
Esta
v&lvula debe estar Iocalizada
en la misma
habitaci6n
en que estb la cocina, en un lugar que
facilite
su apertura
y cierre. El prop6sito
de la
v&lvula es generar o interrumpir
el suministro
de
gas a la cocina. No bloquee el acceso a la valvula
de suministro.
Regulador
de presibn: Se debe usar el regulador
de
presi6n
provisto
con esta cocina.
Para el debido
funcionamiento
de la cocina,
la presi6n
de entrada
al regulador
debe ser como
sigue:
GAS NATURAL:
Presi6n
minima:
5 pulgadas
WCP
Presi6n
mbxima:
14 pulgadas
WCP
GAS de P.L:
Presi6n
minima:
11 pulgadas
WCP
Presi6n
m_xima:
14 pulgadas
WCP
Si no est& seguro
sobre la presi6n de entrada,
consulte
con la compafiia
de gas de su Iocalidad.
11