Haier HWF05XCK Use And Care Manual page 11

Haier air conditioner user manual
Table of Contents

Advertisement

Available languages

Available languages

Air conditioner blows fuses or trips circuit breakers
Too many appliances are being used on the same circuit.
Unplug or relocate appliances that share the same circuit.
Time-delay fuse or circuit breaker of the wrong capacity
is being used. Replace with a time-delay fuse or circuit
breaker of the correct capacity. See "Electrical
Requirements."
An extension cord is being used. Do not use an extension
cord with this or any other appliance.
You are trying to restart the air conditioner too soon after
turning off the air conditioner. Wait at least 3 minutes after
turning off the air conditioner before trying to restart the air
conditioner.
Air conditioner power supply cord trips (Reset button
pops out)
Disturbances in your electrical current can trip (Reset
button will pop out) the power supply cord. Press and
release RESET (listen for click; Reset button will latch and on
some devices, a green light will turn on) to resume operation.
Electrical overloading, overheating, cord pinching or aging
can trip (Reset button will pop out) the power supply cord.
After correcting the problem, press and release RESET (listen
for click; Reset button will latch and on some devices, a green
light will turn on) to resume operation.
NOTE: A damaged power supply cord must be replaced with a
new power supply cord obtained from the product manufacturer
and must not be repaired.
Air conditioner seems to run too much
The current air conditioner replaced an older model. The
to run longer than an older model, but the total energy
consumption will be less. Newer air conditioners do not emit
the "blast" of cold air you may be accustomed to from older
air conditioners, but this is not an indication of lesser cooling
capacity rating (in Btu/h) marked on the air conditioner.
The air conditioner is in a heavily occupied room, or
heat producing appliances are in use in the room. Use
exhaust vent fans while cooking or bathing and try not to use
heatproducing appliances during the hottest part of the day. A
higher capacity air conditioner may be required, depending on
the size of the room being cooled.
Air conditioner cycles on and off too much or does not
cool room in cooling mode
The air conditioner is not properly sized for your room.
Check the cooling capabilities of your room air conditioner.
Room air conditioners are not designed to cool multiple rooms.
There is excessive heat or moisture (open container
cooking, showers, etc.) in the room. Use a fan to exhaust
heat or moisture from the room. Try not to use heatproducing
appliances during the hottest part of the day.
The louvers are blocked. Install the air conditioner in a
location where the louvers are free from curtains, blinds,
furniture, etc.
The outside temperature is below 65°F (18°C). Do not try to
operate your air conditioner in the cooling mode when the
outside temperature is below 65°F (18°C).
The temperature of the room you are trying to cool is
extremely hot. Allow extra time for the air conditioner to cool
off a very hot room.
Windows or doors to the outside are open. Close all
windows and doors.
The Temperature control is not at a cool enough setting.
Adjust the control to a cooler setting to reduce the temperature.
Set the Fan Speed control to the highest setting.
Water drips from cabinet into your house
The air conditioner is not properly leveled. The air
conditioner should slope slightly downward toward the outside.
Level the air conditioner to provide a downward slope toward
the outside to ensure proper drainage. See the Installation
Instructions.
NOTE: Do not drill a hole into the bottom of the metal base
and condensate pan.
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hwf05xck-eHwf05xck-lHwf05xck-t

Table of Contents