Haier AU182AFERA Installation Instructions Manual page 14

Dc inverter outdoor unit
Hide thumbs Also See for AU182AFERA:
Table of Contents

Advertisement

Read Before Installation
Charging Refrigerant
R410A must be in a liquid state when charging.
Reasons :
1. R410A is a pseudo-azeotropic refrigerant (boiling point R32= -52*, R125= -49*) and can
roughly be handled in the same way as R22; however, be sure to fill the refrigerant from the
liquid side, for doing so from the gas side will somewhat change the composition of the
refrigerant in the cylinder.
Note :
* In the case of a cylinder with a syphon, liquid R410A is charged without turning the cylinder
up side down. Check the type of cylinder before charging.
Remedies to be taken in case of a refrigerant leak
When refrigerant leaks, additional refrigerant may be charged. (Add the refrigerant from the
liquid side)
Characteristics of the Conventional and the New Refrigerants
* Because R410A is a simulated azeotropic refrigerant, it can be handled in almost the same
mammer as a single refrigerant such as R22. Howerver,if the refrigerant is removed in the
vapor phase , the composition of the refrigerant in the cylinder will somewhat change.
* Remove the refrigerant in the liquid phase. Additional refrigerant may be added in case of
a refrigerant leak.