Installation of Indoor Unit
ELECTRICAL REQUIREMENT
Electric wire size and fuse capacity:
Select wire sizes and circuit protection from table below. (This table shows 20 m
length wires with less than 2% voltage drop.)
Item
Phase
Model
For series 282, 362
For series 282(EAA)
362
For series 522, 482,
602
Fig. 15
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
(1) Match the terminal block numbers and connection cord colors with those of the
outdoor unit.
Erroneous wiring may cause burning of the electric parts.
(2) Connect the connection cords firmly to the terminal block. Imperfect installation
may cause a fire.
(3) Always fasten the outside covering of the connection cord with the cord clamp.
(If the insulator is chafed, electric leakage may occur.)
(4) Always connect the ground wire.
Circuit breaker
Switch breaker
Overcurrent protector
(A)
1
40
3
30
3
30
Insulation tube
Table 5
Power source
wire size
(minimum)
rated capacity (A)
26
20
20
CAUTION
21
Earth leakage breaker
Switch
breaker(A)
2
(mm
)
6.0
40
2.5
30
4.0
30
Cord clamp
Leak
current(mA)
30
30
20