Static Bypass - GE Digital Energy Datasheet

Sg series uninterruptable power supply 225-300kva ul listed with eboost digital energy
Hide thumbs Also See for Digital Energy:

Advertisement

g
Nominal output voltage
Inverter bridge
Output Isolation transformer
Output waveform
Output voltage tolerance
Output voltage distortion
Crest factor capability
Output neutral rating
Phase displacement
Output frequency
Overload capability (on inverter)
Short circuit capability (on inverter)
UPS Rating
Maximum Output Current @ 0.9pf
Input configuration
Primary components
Transfer limits
Overload capability (on bypass)
Short circuit capability (on bypass)
Input wiring configuration
Output waveform
Transfer time (static bypass to Inverter)
Transfer limits
Steady-state frequency tolerance
Instantaneous phase shift
g
imagination at work
Energy
Digital Energy
Technical Data Sheet - 225-300kVA UL Listed
Load step 0% - 100% - 0%:
Load step 0% - 50% - 0%:
100% unbalanced load (Ph-N):
100% linear load:
100% non-linear load (per IEC 62040):
100% balanced load:
100% unbalanced load:
Free running:
Synchronized with utility:
eBoost™ Operating Mode
Steady-state RMS tolerance
Instantaneous voltage distortion
(with respective to Normal Sine wave)
Inverter
480VAC, 3-phase, 4 wire + ground (NOTE 1)
IGBT technology and Space Vector Modulation
Static:
+/- 3%, recovering to within +/- 1% in 1 cycle
+/-2%, recovering to within +/- 1% in 1 cycle
+/- 4% (adjustable from 57.6Hz to 62.4Hz)
125% at 0.9 PF for 10 minutes.
150% at 0.9 PF for 30 seconds
700% of rated current for first 1.2 ms followed by
220% for 100 ms, electronically limited
225
270.0

Static Bypass

Common with rectifier (default) or dual input (optional)
Full load rated static switch
Back feed protection + Semiconductor fuse for clearing fault currents
Internal maintenance bypass (optional)
+/- 10% of nominal output voltage (adjustable)
1000% for 1/2 cycle (non-repetitive)
480VAC, 3-phase, 4 wire + ground (NOTE 1)
Continuously monitored
+/-20 Vrms (adjustable)
Magnitude
Duration
0.15 radians (8.5 Deg)
Standard
True sine wave
+/- 1%
+/- 3%
2% THD maximum
3% THD maximum
< 3:1
200%
120°+/- 1%
120°+/- 2%
60Hz, +/- 0.01%
300
360.0
110% continuous
200% for 5 minutes
<4ms (typical)
+/-75Vp
500µs (adjustable)
+/-3 Hz
GEA-D2041 (225 300kVA TDS), Page: 3
(kVA)
A

Advertisement

loading