compressor, indoor fan run 5 minutes in low speed. And repeat on and off cycle.
8.8.3 Low room temperature protection:
When room temperature decreases to below 10℃, the compressor and the outdoor fan
will stop(indoor fan is Breeze). Dehumidifying operation will be resumed when room
temperature restores to over 13℃.
8.8.4 Under dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the
same as that of cooling mode.
8.9
Heating mode
8.9.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode.
4-way valve must delay 2 minutes compared with compressor if the compressor changed
into non-heating mode or turned off. 4-way valve doesn't delay in dehumidifying mode.
8.9.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating
mode, except for the defrosting mode or the end of defrost.
8.9.3 Action conditions of compressor under heating mode: compressor must run for 7
minutes after starting and then judge temperature. Meanwhile other protections are still
valid.
Room temp. up
Room temp. down
TA: Indoor ambient temperature
TS: Setting temperature through the remote controller
8.9.4 Indoor Fan actions under heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but
Anti-cold wind function has the priority.
Anti-cold wind control function under heating mode
Indoor exchanger temp. up
Indoor exchanger temp. down
TE: Indoor evaporator temperature
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
Condition
Compressor
TA> Ts+3
TA<Ts+3
TA< Ts+2
TA>Ts+2
Condition
TE
TE<TE1
TE1<TE<TE2
TE>TE2
TE> TE3
TE3<TE<TE4
TE<TE4
Page 18 of 33
Outdoor fan
Off
Off
On
On
On
On
Off
Off
Indoor fan speed
Off
Breeze
Setting fan speed
Setting fan speed
Breeze
Off