6.7.2 WIRING

• Wiring should be of stranded copper to reduce the
chance that vibration may cause breakage.
• Wire gauge size should be large enough to handle
at least 115 percent of the installed generator's
rated maximum current.
• If neutral conductors are used, they must be the
same size as other leg wires.
• Route power supply conductors from generator AC
output leads T1 (red), T2 (white), T3 (black) and
the green ground wire through approved flexible
conduit to the electrical junction box on the com-
partment wall.
• If flexible metal conduit is used between the gener-
ator and the compartment junction box, the con-
duit end that terminates the compartment junction
box must be vapor-sealed. Flexible metal conduit
is NOT vapor tight along its entire length.
• From the junction box, route power supply wires
through approved conduit to either (a) double-
pole, double-throw transfer switch, or (b)
approved isolation receptacle. Connecting to a
transfer switch or isolation receptacle must pre-
vent vehicle electrical circuits from being connect-
ed to two different power supplies at the same time
(such as generator and dockside power).
• Conductors must be rated 221° F (105° C) or must
be of a larger conductor size.

6.7.3 GENERATOR AC CONNECTIONS

Generator AC output leads T1 (red), T2 (white) and
T3 (black) come out of the generator as shown in
Figure 6.18. Leads T1 (red) and T3 (black) are "hot,"
while T2 (white) is the grounded neutral lead. There
is also a green lead that connects to ground in the
junction box of the recreational vehicle.
Figure 6.18 – Generator AC Output Leads
QUIETPACT 55, 65, and 75 Recreational Vehicle Generators
Line T1 (red) to T2 (white) is protected against over-
load by a circuit breaker (CB1). Use this line-to-neu-
tral connection separately to operate 120-volt, single-
phase, 60 Hertz, AC loads. Line T3 (black) to T2
(white) also is protected against overload by a circuit
breaker (CB2). Use this line-to-neutral connection
separately to operate similar loads. However, be sure
the total unit load does not exceed the maximum rat-
ing of the generator. The neutral line (T2, white) on
all units is a grounded neutral.
Route the connections between the generator and the
junction box through approved, flexible conduit. The
following general rules apply:
• Cut wiring to the required length and allow extra
• Carefully prepare conduit ends to prevent sharp
• Route conduit so it does not interfere with genera-
• If you use metallic conduit, vapor seal the end of
Connections from the junction box must terminate in
a double-pole, double-throw transfer switch (Figure
6.19, Page 33). An alternate method for isolating dif-
T3
ferent power sources is by using an isolating recepta-
T2
T1
cle (Figure 6.20, Page 33). Whichever method you
Green
use, you must be certain that both power sources are
(Ground)
NOT connected at the same time.
The power supply cord must comply with all applic-
able codes, standards and regulations. It must be
large enough to handle the full amperage to which it
will be subjected. (See page 33 for illustration.)
Section 6 – Installation
Do NOT connect electrical loads in excess of
any circuit breaker rating or you will develop
problems with circuit breaker tripping, which
causes a loss of AC output. Also, do NOT
exceed the generator's rated wattage capacity.
Add the watts or amperes of all lighting, appli-
ance, tool and motor loads the generator will
operate at one time. This total should be less
than the unit's rated wattage/amperage capaci-
ty.

6.7.4 CONDUIT

wire for junction box connections.
edges from cutting through wiring insulation.
tor movement.
the conduit where it enters the junction box. Do
this because flexible metallic conduit is not vapor-
proof along its entire length.
6.7.5 ISOLATING DIFFERENT POWER
SOURCES

6.7.6 POWER SUPPLY CORD