Essential Elements Ordering Overview

20/208-volt line-cord connected units — order line cord kit.
20/208-volt sub-base connected units — order sub-base
(includes power connection kit) and junction box for chassis.
265-volt units — order sub-base and power connection
kit separately.
Electrical Wiring Information –
2900/900/5800 Series
All Zonelines are single-phase 60 hertz units.
For all installations, the feeder, sub-feeder, branch circuit and
electrical protective devices and selection must conform to
the National Electrical Code and to local codes.
Maximum connected load in amperes, including demands
for the electric heater and the fan motor, are shown on page
44. Branch circuit ampacity and electrical protective device
sizing are shown on page 42 for 20/208-volt units and on
this page for 265-volt units.
More than one unit per branch circuit is not recommended.
When in doubt, consult the National Electrical Code. All
wiring, including installation of receptacle, must conform
to local electrical regulations and codes.
Replacement of Existing Chassis
230/208-Volt and 265-Volt Units
There have been changes to NEC and improvements and
modifications to the Zoneline chassis and sub-bases since
the unit was first introduced. Some of these changes require
alterations to be made when replacing an older unit with a
new chassis.
Line-Cord Connected Units
The plug configuration of new line cord connected units
complies with the current NEC standards. Older installations
may have wall receptacles that conformed to NEC standards
at the time the building was constructed and may not match
the configuration of the plug on the new line cord. The
recommended solution is to change the wall receptacle to
conform to current standard plug configuration. See chart
on this page for current receptacle configuration.
58"
21"
Inside
Typical Line Cord
Power Connection Kit
Maximum Cord Extension
RAK20 shown
ge.com
Permanent Connected Units With Sub-Base
If the existing unit is connected to a sub-base the installation
of the new unit may involve modifying the existing installation
slightly. It is recommended these modifications be made by a
qualified electrician.
If the existing sub-base is the full width of the wall case,
RAK201 sub-base access plate may be ordered and used
to replace the cover on the old sub-base. Field-supplied
wiring, conduit and conduit connectors should be used to
make a connection between the new chassis and the center
knockout of the RAK201. The wiring connections should be
made inside the sub-base and the RAK201 attached to the
sub-base with the two screws provided.
If the existing sub-base is not the full width of the wall case,
the electrician will have to modify the existing cover plate to
allow field-supplied wiring, conduit and conduit connectors to
be run from the permanent connection kit to the sub-base.
Enclosure cover removed.
RAK4002A
Wiring harness can be ordered separately as RAK4002CW.
Receptacle
Type
Mfg
Part No
Configuration
15 AMP
Hubbell
5661
Tandem
P&S
5661
NEMA6-15R
20 AMP
Hubbell
5461
Perpendicular
P&S
5871
NEMA6-20R
0 AMP
Hubbell
90
Large Tandem
P&S
590
NEMA6-0R