16.0 Specifications

Table 12: D6600/D6100i Specifications
Dimensions
D6600
(H x W x D)
D6100i
Weight
D6600
D6100i
AC Nominal Operating Range
D6600 Power Input
AC Maximum Operating Range
AC Nominal Operating Range
D6100i Power Input
Current Required
D6600 with one line card installed
For each additional line card or terminal
card pair
For network communications card
D6100i
Use a UPS with the D6600/D6100i. The receiver includes an external battery connection and battery harness. Use
Standby Power
12 V rechargeable sealed lead-acid batteries. A 4-hour minimum standby power supply (UPS or battery) is required
for UL Certification (refer to Section 8.1 Connecting External Batteries on page 14 for battery size).
Telephone
RJ11C modular jacks, with 26 AWG or larger wire diameter.
FCC Registration
D6600 ESVUSA-25328-AL-N
D6100i ESVAL04BD6100
The D6600 Receiver is Federal Communications Commission (FCC) registered under Part No. 68 using the
RJ11C Interconnect that can be ordered from your local telephone company.
Notice: This equipment has been tested and found to comply with the limits for a Class A (D6600) or Class B
(D6100i) digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
Any modifications made to this device that are not approved by Bosch Security Systems, Inc. may void the authority
granted to the user by the FCC to operate this equipment.
Ringer Equivalence
0.4 B
Bosch Security Systems, Inc. | 8/07| 4998122704-02
Conettix D6600/D6100i | Installation and Operation Guide | Contents
Rack mount (4U)
Standalone
Rack mount (2U)
Standalone
8.7 kg (19 lb)
3 kg (7 lb)
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
18 cm x 48.3 cm x 49.5 cm
(7.0 in. x 19.0 in. x 19.5 in.)
18 cm x 45.0 cm x 49.5 cm
(7.0 in. x 17.75 in. x 19.5 in.)
9.0 cm. x 37.5 cm. x 25.5 cm
(3.5 in. x 19 in. x 10 in.)
9.0 cm. x 30.5 cm. x 25.5 cm
(3.5 in. x 12.0 in. x 10 in.)
120 V or 230 V
100 VAC to 120 VAC, 220 VAC to 230 VAC, 50 - 60 Hz
2.5 A maximum
18 VAC, 40 - 50 VA Transformer
Required battery current
Required UPS AC standby current
Required additional battery current
Required additional UPS AC standby current
Required additional battery current
Required additional UPS AC standby current
Required battery current
Required UPS AC standby current
800 mA
350 mA
210 mA
35 mA
10 mA
10 mA
330 mA
180 mA
33