Conettix D6600/D6100i | Installation and Operation Guide | 8.0 Standby Power
10. Turn the D6600 power switch on. The D6100i
starts as soon as you plug in the AC Transformer.
11. Set the calendar and clock to the correct date and
time and program the necessary options.
12. Ensure that the communication formats are correct
by having communicators send test reports to each
line connected to the receiver.
7.6

Rack Mount Instructions

Rack mounting hardware is included with the D6600,
and is available as an option with the D6100i
(D6100i RMK). When mounted in a rack, plug the
D6600 AC cord or the D6100i AC transformer into an
outlet inside the rack only if the outlet is wired
according to Article 760 of the NEC. Rack mounting is
required (per NFPA 72, 1-5.2.5.2) to meet the
mechanical protection requirement when using the
type of AC cord provided with the D6600. It is also
required that a UL Listed rack for fire protective
service be provided when used in UL Listed central
stations.
Do not connect the D6600/D6100i to an
outlet controlled by a switch.
7.7

Removing Power to the Receiver

1. Remove the battery power connection.
2. Turn off the AC power on the D6600 or unplug
the D6100i AC transformer.
3. Unplug the AC cord from the outlet.
Do not try to restart the D6600/D6100i
with a fully discharged battery. Reconnect
after you apply power. To prevent deep
battery discharge, use a D135A Low
Battery Cutoff Module. Refer to the
D135A Installation Guide (P/N:
74-06499-000) for more information.
If programmable Output 1 or 2 is
activated by automation failure, you
cannot clear Output 1 or 2 by pressing
the [ACKNOWLEDGE] key.
14

8.0 Standby Power

During a loss of AC power, the receiver automatically
switches to standby power. External batteries or an
uninterruptible power supply (UPS) provides standby
power. As long as there is adequate standby power, the
receiver's operation is not interrupted, even if the
power loss occurs during signal processing. When
power supervision is enabled and a loss of AC power
occurs, the primary reporting devices (such as printers
and computers) show AC FAIL and the D6600/D6100i
power indicator starts blinking. When AC power
restores, the power indicator stops blinking and
reporting devices show AC RESTORE.
8.1

Connecting External Batteries

Do not connect an external battery
charger to the D6600/D6100i or its
battery.
Use the terminal on the rear panel to connect an
external DC power source. During AC power outages,
the external DC source supplies power to the receiver.
Use a 12 VDC lead-acid battery for external backup
power.
Only use approved stationary standby batteries for UL
applications. Battery wiring must run from the receiver
through the UL Listed rack, exit the rack through a
conduit connection, and terminate at a UL Listed
battery enclosure suitable for the size and number of
batteries used for UL applications.
Table 5: Battery Voltage Display
Battery Voltage
Display during
AC power outage
Above 11.5 V
Battery OK
11.5 V to 10.2 V
Battery Low
Below 10.2 V
Battery Bad
Bosch Security Systems, Inc. | 8/07 | 4998122704-02
Display if no
battery when
AC power is
restored
Battery
Missing