Gas Piping - Kenmore POWERMISE 12 Owner's Manual

74 gallon (280 liter)
Table of Contents

Advertisement

• For proper draft hood attachment, the draft hood legs may
be angled slightly inward.
• Place the draft hood legs in the receiving holes on the top
of the water heater. The legs will snap in the holes to give a
tight fit. Secure the legs of the draft hood with the supplied
draft hood brackets.
• Place the vent pipe over the draft hood. With the vent pipe
in position, drill a small hole through both the vent pipe and
draft hood. Secure them together with a sheet metal screw,
see Figure 18.
FIGURE 18.
Obstructed or deteriorated vent systems may present serious
health risk or asphyxiation.
The vent pipe from the water heater must be no less than the
diameter of the draft hood outlet on the water heater and must
slope upward at least 1/4 inch per linear foot (21 mm per meter),
see Figure 19.
FIGURE 19.
All vent gases must be completely vented to the outdoors of the
structure (dwelling). Install only the draft hood provided with the
new water heater and no other draft hood.
Vent pipes must be secured at each joint with sheet metal screws.
There must be a minimum of 6 inches (153 mm) clearance
between single wall vent pipe and any combustible material.
Fill and seal any clearance between single wall vent pipe
and combustible material with mortar mix, cement, or other
noncombustible substance. For other than single wall, follow
vent pipe manufacturer’s clearance specifications. To insure a
tight fit of the vent pipe in a brick chimney, seal around the vent
pipe with mortar mix cement.
Failure to have required clearances between vent piping and
combustible material will result in a fire hazard.
Be sure vent pipe is properly connected to prevent escape of
dangerous flue gases which could cause deadly asphyxiation.
Chemical vapor corrosion of the flue and vent system may
occur if air for combustion contains certain chemical vapors.
Spray can propellants, cleaning solvents, refrigerator and air
conditioner refrigerants, swimming pool chemicals, calcium
and sodium chloride, waxes, bleach and process chemicals
are typical compounds which are potentially corrosive.
Gas Piping
Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gas pressure must not exceed
14 inch water column (3.5kPa) for natural gas. The minimum inlet
gas pressure listed on the rating plate is for the purpose of input
adjustment. If the gas control valve is subjected to pressures
exceeding 1/2 pound per square inch (3.5kPa), the damage
to the gas control valve could result in a fire or explosion from
leaking gas.
If the main gas line shut-off serving all gas appliances is used, also
turn “OFF” the gas at each appliance. Leave all gas appliances shut
“OFF” until the water heater installation is complete.
A gas line of sufficient size must be run to the water heater.
Consult the current edition of National Fuel Gas Code ANSI
Z223.1/NFPA 54 and your gas supplier concerning pipe size.
There must be:
Page 16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powermiser 12153.331761

Table of Contents