FLUXPOWER HPS
3-PHASE UPS
OPTIONAL (External Manual bypass)
1
F
5
3xL-N
2
F
3xL
PE
+B -B
3
"Green" double
protection for every
application
VFI online double conversion
topology in this equipment
offers built-in inverter galvanic
protection completely isolating
the output power from all
input power anomalies,
delivering fully conditioned
pure sine-wave output.
In pure on-line mode the unit
delivers an excellent certified
96 % efficiency. Because of
the technology and topology
used, no additional losses are
generated to achieve low input
harmonics or input / output
galvanic isolation.
The Fluxpower HPS unit is
designed to provide excellent
output voltages suited to very
demanding applications
with either 100 % step load,
unbalanced, non-linear
or modern IT loads. It also
provides exceptional
performance: with a power
factor of up to 0.9 (lagging
or leading), there is no
requirement to de-rate the unit.
Triple Intelligence
If the application requires
extremely flexible and
reliable UPS protection,
the Fluxpower HPS is ideal.
It delivers advanced features
based on state-of-the-art total
digital control. This control
incorporates dual DSP (Digital
Signal Processing) and µC
(Micro controller) technologies.
The system design ensures that
auxiliary power supplies and
processors are no longer single
points of failure which could
compromise the availability
of clean power to the load.
F
6
4
3xL-N
The Fluxpower HPS is
designed to overcome the
limitations imposed by other
older, designs. With its
distributed control architecture,
Fluxpower HPS will always
have a UPS circuit protecting
the load; furthermore,
the status of most critical
components is constantly
monitored, allowing predictive
maintenance and avoiding
unexpected breakdowns.
Fluxpower HPS' working state
can be easily monitored by
any Building Management
System and via LAN / WAN.
Life-prolonging
Battery Management
Batteries are electro-chemical
devices, which store charge
chemically; as such their
performance degrades with
time. The Fluxpower HPS owns
a Battery Anti-Aging Control
(BAAC) according to battery
manufacturers' requirements.
Following a UI characteristic
curve, the charger charges at
a constant current appropriate
for the battery type used,
preventing detrimental
excess charging. In addition
to the float voltage level,
boost charge can be set,
optimizing the recharge time
when there is the possibility
of consecutive power outages
within a short period.
BAAC also reduces the
residual ripple current (one
of the causes of premature
battery wear), as well as
protecting the battery from
damaging deep discharges.
1. Input mains (separate for by-pass and rectifier)
2. Rectifier and battery charger
3. External battery
4. Inverter
5. Emergency line (by-pass) with optional backfeed
contactor
6. Inverter (SSI) and by-pass (SSB) static switch
It is possible to install an external manual bypass,
either in the matching cubicle or in wall mounted box
(bypass switch auxiliary contact must be connected
to UPS related input port for status monitoring).
Automatic battery temperature
compensation charge voltage
may be implemented,
charging the battery more
appropriately and increasing
battery life. By means of DCM
(Dynamic Charging Mode)
very long battery autonomies
can be achieved without
increasing total charge time.
This is achieved through
the implementation of an
intelligent increase in maximum
battery charge current when
the maximum inverter power is
not being drawn by the load.
An integrated periodical
battery testing function tests
and monitors battery health,
providing advanced warning
to guide the application of
preventive maintenance.

Parallel systems

with "hot swap"
modularity
Fluxpower HPS UPS offers
parallel options in both
redundancy and capacity
modes, providing the
possibility for both extra
system resilience and
increased capacity.
The parallel control circuitry
associated with these units
is fully digital and acts on
both active and reactive
power on each of the three
output phases. This allows
accurate load current sharing
among the UPS units even
during transient conditions.