Operation Modes - GE Digital Energy LP 33 Series Operating Manual

50 & 60 kva
Hide thumbs Also See for Digital Energy LP 33 Series:
Table of Contents

Advertisement

3.2

OPERATION MODES

This section describes the different possible operation modes of the UPS explaining the function of the
main modules of the UPS.
VFI (Voltage Frequency Independent) Mode operation
Under
normal
conditions
permanently powered by the inverter with
constant amplitude and frequency.
The rectifier, powered by the mains, supplies the
inverter and the battery-charger keeps the
battery fully charged.
The inverter converts the DC voltage in a new AC sine wave voltage with constant amplitude and
frequency independently from the input mains power.
ECO Mode operation (Intelligent Energy Management)
When the ECO Mode is selected, and the mains
power is available, the load is normally powered
through the automatic bypass.
When the mains voltage is detected out of the
prescribed tolerances, the load is automatically
transferred to the inverter.
When the mains recovers, the load returns to
the automatic bypass after a variable time
defined by the control unit.
The ECO Mode can be configured directly by the user for higher efficiency, considering the mains
reliability and criticality of the load.
The selection between the two operation modes "VFI Mode and ECO Mode", or switching between
operation modes at required time, can be done through the UPS control panel (see Section 6.3.1-5).
In case of parallel system
ECO Mode cannot be enabled for RPA Parallel System.
Attention:
A single unit equipped with a RPA - Parallel board, must be considered as parallel, thus
disabling ECO Mode.
Modifications reserved
OPM_LPS_3UO_50K_60K_0US_V010.doc
the
load
is
Fig. 3.2-1 Energy flow in VFI Mode operation
Fig. 3.2-2 Energy flow in ECO Mode operation
Operating Manual LP 33 Series 50 & 60 kVA