Powering Up Procedure - HP Cluster Platform Interconnects v2010 Manual

Myrinet system interconnect guide
Hide thumbs Also See for Cluster Platform Interconnects v2010:
Table of Contents

Advertisement

To power up a Myrinet system interconnect, plug the power cord into the standard
C14 power jack labeled 100–127/200–240 V-. The power cord is rated 10A for the
5U interconnect, and 15A for the 9U chassis. There is no power switch on the
enclosure, which prevents an accidental network shutdown.
Typical operating temperatures for the components of the switch are in the range
of 30–39 degrees Celsius (86–102 Fahrenheit). If you see temperatures in the range
of 50–55°C (122–131°F), the switch is too hot and shutdown may occur. Shutdown
occurs at 55°C (131°F) and operation resumes at 50°C (122°F).
The temperatures reported by the monitoring line card are not air temperatures,
but are the temperatures of the line card circuit boards on which the thermometer
chips are mounted. Hence, the temperatures reported are very close to the
temperatures of the components on the circuit boards. If the inlet air temperature
is 40°C (104°F), the monitoring line card circuit-board temperatures may be as
high as 50°C (122°F), even on the inlet side.
Interconnect specifications
The following table presents the operating and performance specifications for the
Myrinet system interconnect:
Characteristic
Maximum BTUs per hour
(with line cards in all slots)
Watts
Max input current (100 to
127V)
Max input current (200 to
240V)
Height (1U = 1.75 inches =
44.45 mm)
Width
Depth
Weight without line cards
Weight with line cards in all
slots
Fans on fan tray
Total air flow
Temperature Range (all sizes)
Operating
Shipping
Relative Humidity (all sizes, noncondensing)

Powering up procedure

5U Chassis
1680
480
4.8A
2.4A
5U
43.6 cm/17.18 in
44.5 cm/17.5 in
10 kg/22 lb
15 kg/33 lb
4 92mm
120 cfm
41°F to 104°F
-40°F to 158°F
6
9U Chassis
3360
960
9.6A
4.8A
9U
43.6 cm/17.18 in
44.5 cm/17.5 in
21 kg/46.3 lb
31 kg/68.3 lb
8 92mm
240 cfm
Powering up procedure
6-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cluster platform

Table of Contents