Initial Startup With Bodac - Bosch Rexroth VT-VRPD-2 Installation & Operation Manual

Digital valve amplifier for valve types, 4wre 6 & 10, component series 2x
Table of Contents

Advertisement

22/32
Bosch Rexroth AG | Hydraulics
3 Startup of the VRPD Controller Card
3.3

Initial startup with BODAC

After installing the VRPD controller card in a rack, as described in section 2.4 "Card
Installation", and all initial steps have been completed properly, the card startup is
ready.
Before proceeding with the following steps, be sure that the following requirements
have been met:
Serial interface cable is available
A serial port on the PC is available
BODAC software is installed.
Proceed with the initial startup:
Connect serial cable (ordering number R900776897) to the connector on the
VRPD card.
Plug serial cable into the serial port (COM) on the PC (or use USB-converter –
S/N R90166684).
The VRPD card and PC are now connected.
Start the BODAC software.
Perform the software-side startup as described in the "Starting up the VRPD
Control Card and Operation of the BODAC Soft-ware" document.
Installation and Operation | RE 30126-B/09.13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents