4200Fa 30 Kva W/Internal Transformer - Toshiba 4200 FA CT User Manual

Three-phase 15/25/30/50 kva ups
Table of Contents

Advertisement

5.4

4200FA 30 kVA w/Internal Transformer

Model Number
Rated Output Capacity
External Dimensions
W x D x H (cm)
Input
Rated Voltage
Voltage Variation
Rated Frequency
Input Cables Required
Dual Input Option Cables required
* Power Factor
Required Input kVA
Walk-in Function
Inrush Current
Current Limit
* Harmonic Currents
Battery
DC Nominal (Voltage Range)
Float Charge (Regulation)
Ripple Voltage
**Rated Back-up Time
Rated Charge Current
Output
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronous
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 ms)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
Harmonic Voltage Distortion
Inrush Current protection
Environment
Efficiency (Typical)
Heat loss to be removed
Audible Noise
Operating Temperature
Operating Humidity
Altitude ***
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
(****) Prolonged operation at this level requires some derating of the output capacity.
4200FA CT/XT User's Manual
TOSHIBA
# =(B: 208; H: 220; C: 240; N: 380–415 Δ-wye; P: 380–415 wye;
Input
*=(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye:
Output
208; 220; 240; 380; 400; 415; 480; 600 VAC
(Determined by Input Transformer internal to the unit)
Less than 8 times the rated current under synchronous operation
(Determined by Output Transformer internal to the unit)
Automatic Transfer to bypass, then retransfer to inverter
60dB (A) at 1 meter from the front of the unit
32 – 104 °F (0 – 40 °C); optimal temperature is 77 °F (25 °C)
T42#3*300#AMXN
D: 480; M: 600) VAC
M:600) VAC
30 kVA
20.0" x 36.3" x 59.7"
(50.8 cm x 92.2 cm x 151.6 cm)
+10% to -30%; (-15% to -30%****)
50/60 Hz
3 phase ; 3 Wire + GND
3 phase ; 4 Wire + GND
Greater than 0.98 when in inverter mode
30.5 kVA
From 20% to 100% over 5 seconds
115% maximum
Less than 3% THD
288 VDC (216 to 332 VDC)
324.0 VDC (± 2%)
0.5 V R.M.S.
Refer to Battery System Manual
10.0 Amps
VA / Nominal Output Voltage / 1.73
0.8 lagging
3 phase ; 4 Wire + GND
± 5% (0 – 100% balanced load);
± 6% (0 – 100% unbalanced load)
± 5V Manually from key pad
± 2° (0 – 100% balanced load);
± 4° (unbalanced load)
50 / 60 Hz
± 0.1% in free running mode
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.)
switch selectable by qualified technician
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
± 5% (100% load step change);
± 3% (loss or return of input voltage);
± 8% (transfer from bypass to inverter)
125% for 90 sec; 150% for 30 sec
1000% for 10ms; 125% for 10 min.
2.5 – 3.0 within the kW range
1.73 (200%) times line rating
1.5% max (linear load)
AC/DC/AC: 77%; DC/AC: 83%
23,216 BTU/hr (5,849 kcal/hr)
30 – 90% RH (non condensing)
Less than 2000 meters
29