431B Backup Runtime Tables - Toshiba 431A Installation And Operation Manual

4300 series ancillary cabinets
Table of Contents

Advertisement

1. Run the pre-wired shunt trip cable shown in Figure 11.7 from the 431B through the 431B/UPS cable
access port located at the bottom left side of the 431B, to the UPS 24VDC power supply on the lower
left side of the UPS.
2. Plug the shunt trip cable connector into the shunt trip receptacle in the lower left front of the UPS.
(The connectors are keyed to only plug in one way.)
3. Reinstall the dead fronts.
11.7

431B Backup Runtime Tables

The following give the typical backup runtimes at various loads for a single cabinet 431B.
UPS
Capacity
PF
4300
30kVA
0.8
4300
30kVA
0.9
4300
50kVA
0.8
4300
50kVA
0.9
38
Runtime in Minutes at % Full Load
100%
90%
80%
70%
17
21
24
15
17
20
8
9
11
7
8
9
4300 Series Ancillary Cabinets Installation and Operation Manual
Figure 11-7 - 431B Factory Supplied
Shunt Trip Wiring
60%
50%
40%
30
38
45
59
24
33
38
53
14
17
24
32
11
15
20
26
30%
20%
10%
>90
>90
>90
74
>90
>90
46
70
>90
44
60
>90