PRIMARY
SENSOR
THROTTLING
RANGE
COMPENSATION
SENSOR
COMPENSATION
START POINT (WC)
Fig. 11. Positive (Summer) Compensation Calibration
Reset Schedule, Direct Acting Controller-3 to 13 psi
(21 to 90 kPa) Throttling Range.
6.
Adjust the restrictor for the equivalent pressure of
the primary sensor at the compensation startpoint
on the reset schedule.
Adjust the setpoint knob until the BLP equals the
7.
desired BLP at the compensation start conditions
(e.g., 13 psi [90 kPa] for negative compensation, 3
psi for positive compensation).
If needed, remove the setpoint knob and reposition
8.
it so the setpoint matches the primary sensor value
at the compensation start. The setpoint knob is
calibrated.
Supply the adjustable restricted air (equivalent to
Controller Calibration Kit MQP816A) to Port 5
(compensation sensor).
Adjust the restrictors for the equivalent pressure of
10.
the sensors at full compensation on the schedule.
11. Adjust the authority knob until the BLP equals the
desired pressure of the controlled device with full
compensation conditions.
NOTE: This point can be slightly different from
the calculated authority set on the control
ler. Leave the new setting on the controlIer
and mark the job drawings with the new
value.
12. Calibration is complete.