Download Print this page

Technical Specifications - Bosch LBB 1990/00 Use Manual

Plena voice alarm controller
Hide thumbs Also See for LBB 1990/00:

Advertisement

2 | LBB 1990/00 Plena Voice Alarm Controller
Each message can have any length within the total
available capacity. Messages and configurations are
uploaded from a PC via USB into the memory, after
which the unit operates without PC connection. The
standard WAV-format is used for the messages and
sample rates of 8 kHz up to 24 kHz with 16-bit word
length (linear PCM) are supported. This gives up to 17
minutes of recording time with CD-quality signal-to-
noise ratio.
The unit has 12 contact trigger inputs for business and
emergency (EMG) calls. Each can be configured for a
message consisting of a sequence of up to 8 wave files.
In this way some wave files may be used in different
combinations with other messages, optimizing flexibility
and used storage space. Multiple messages can be
merged to form one integrated message. Together with
this sequence, for each trigger input, a zone selection
can be configured.
Certifications and Approvals
EMC emission
EVAC compliance
EMC immunity
Safety
Installation/Configuration Notes
Rear view
Parts Included
Quantity
Component
1
LBB 1990/00 Plena Voice Alarm Controller
2
19"Mounting brackets
1
Mains cable
1
Plena CD
acc. to EN 55103-1
acc. to IEC 60849
acc. to EN 55103-2
acc. to EN 60065

Technical Specifications

Electrical
Mains Voltage
230 / 115 VAC, ±10%, 50 / 60 Hz
Main Power Consumption
60 VA
Max/Rated Output Power
360 W / 240 W
Battery Current
24VDC, +20% / -10%
Max Mains Inrush Current
8A @ 230 VAC / 16A @ 115 VAC
Mains Current
System Idle
0.26 A = 60 VA
System Idle with Pilot Tone
0.6 A = 136 VA
Maximum Load*
3.6 A = 830 VA
)
24 V Current
System Idle
0.9 A
Maximum Load*
14 A
Performance
Frequency Response
60 Hz – 18 kHz (+1/-3 dB, @ -10 dB ref. rated
output)
Distortion
<1% @ rated output, 1 kHz
Bass Control
-8/+8 dB @ 100 Hz
Treble Control
-8/+8 dB @ 10 kHz
Inputs Mic / Line
Input Type
XLR, 6.3 mm jack
Sensitivity
1 mV / 1V
S/N
63 dB (flat at max volume)
S/N
75 dB (flat at min volume/muted)
Headroom
25 dB
Speech Filter
-3 dB@ 315 Hz, high-pass, 6 dB/oct
Phantom Power Supply
12 V
VOX Trigger Level
–20 dB (100 V mic / 100 mV line)
or via input contact
Limiter
Automatic
BGM and PC Call Station
Input Type
Cinch stereo (converted to mono)
Input Level
200 mV – 2 V
Impedance
22 kOhm
S/N
70 dB (flat at max volume)
S/N
75 dB (flat at min volume/muted)
Headroom
25 dB
Trigger Inputs
6 EMG, 6 business
Type
MC1,5/14-ST-3,5
Activation
Programmable
Supervision
On EMG inputs, programmable
Supervision Method
Series / parallel resistor
100 V Input
MSTB 2,5 /16-ST
Power Handling Capacity
480 Watts
*) Maximum load means; maximum power out, maximum load 24V out, maximum number of
call stations

Advertisement

loading