Bosch GWH 2400 ES NG User Manual page 10

Indoor model temperature modulated with electronic ignition suitable for heating potable water only
Hide thumbs Also See for GWH 2400 ES NG:
Table of Contents

Advertisement

Installation instructions
Recommended exhaust vent terminator position
Fig. 10
Ref.
Description
Directly below an opening; operable windows, doors and any non-
A
mechanical fresh air openings
Below a gutter, sanitary pipework or eaves
B
Below a gutter, sanitary pipework or eaves, protected by metal
shielding
C
From any internal corner
Above ground or snow pack
D*
Above a paved sidewalk
From an opposing wall or structure facing the termination
E
From the relief valve of a Ip gas regulator
F
From a terminator facing a terminator
G
Vertically between two exhaust vent terminators on the same wall
H
Horizontally between two exhaust vent terminators on the same wall
Horizontally and vertically from combustion air inlet of a twin pipe
system
I**
From the gravity combustion air inlet any other equipment
J
From any external corner
Horizontally from an opening; operable windows, doors and any non-
K
mechanical fresh air openings
Vertically from a wall, roof slope, or obstruction (venting through a flat
L
or pitched roof)
Table 6
* Subject to local codes and anticipated snow level
** Other equipment that operates with a mechanical air inlet may require greater distances, reference manufacturer's instructions
NOTE: terminating exhaust vent under a deck is not permitted
10
Minimum distance
36 in (twin pipe installation)
48 in (single pipe installation)
24 in
12 in
12 in
12 in
7 ft
24 in
60 in
48 in
60 in
36 in
36 in
6 ft
12 in
12 in (twin pipe installation)
48 in (single pipe installation)
see ABOVE THE ROOF
requirements on following page
6 720 608 782