Ul Standard 864 For Fire System Installations - Bosch Conettix C900V2 Installation Manual

Dialer capture ethernet module
Hide thumbs Also See for Conettix C900V2:
Table of Contents

Advertisement

Conettix C900V2 | Installation Guide | 7.0
.
7.0 UL Standard 864 for Fire
System Installations
To install the C900V2 in compliance with UL 864
for Fire System Installations, you must satisfy all
requirements in this section. You must install the
system in accordance with NFPA-72.
If the control panels are used for fire applications,
test according to NFPA-72.
For UL Listed Fire Installations, shared
on-premises communications
equipment must be UL Listed for
Information Technology Equipment.
Installation at the Protected Premises
1. Use the D6200 Software to set the poll rate on
the C900V2. For UL approved installations, the
maximum interval is 90 seconds to meet the
requirement for polling supervision established
by UL. In most cases, to get a polling
supervision interval of 90 seconds, set the Poll
Rate to 75 and Retry to 13.
(For non-UL approved installations, the
maximum interval is 300 seconds to meet the
requirement for polling supervision set by
NFPA Standard 72, Section 5-5.4.4.1. To get a
polling supervision interval of 300 seconds, set
the Poll Rate to 240 and Retry to 13.)
Because of differences in packet transmission
time latency within different networks, the poll
rate times vary. Contact Technical Support at
Bosch Security Systems, Inc. for help in
establishing the latency time for the network on
which you are installing the C900V2.
Refer to D6200 Software Operation and
Installation Guide (P/N: 4998154991).
2. Set DIP Switch 7 to the OFF position to enable
75-second supervision signals.
Refer to Table 5 on page 10 for the
functions of DIP Switches 5 through 9.
3. Add a telnet password to the communications
protocol of the C900V2 (refer to Section 4.5.3
Configuration Using Telnet, step 6, on
page 16). Retain the password for future
reference.
Bosch Security Systems, Inc. | 8/08 | F01U087780-01

UL Standard 864 for Fire System Installations

4. Program the control panel to send a daily test
signal through the digital dialer.
This tests the connection from the
control panel to the C900V2.
5. Connect Output 1 from the C900V2 to a
24-hour zone on the control panel.
This enables the control panel to
annunciate a C900V2 CPU failure
locally.
6. Connect Output 2 from the C900V2 to a
24-hour zone on the control panel.
This enables the control panel to
annunciate a network failure locally.
You must use the C900V2 with a UL
Listed Fire Alarm Control Unit or a UL
Listed combination Fire/Burglary Alarm
Control Unit with an integral or UL
Listed digital alarm communicator
transmitter (DACT). Refer to the
C900TTL-E and C900V2 Compatibility
Chart
(P/N: 4998141056).
7. If the C900V2 is installed in a separate
enclosure, you must locate the unit in the same
room within 6.1 m (20 ft) because the control
equipment and the wiring must be enclosed in
conduit (or equivalently protected against
mechanical injury).
Mounting a C900V2 in a control panel
enclosure is approved by UL only when
used with a DS 7400Xi as shown in
Figure 5 on page 6.
8. You must use the C900V2 with a UL Listed
Power Supply (such as Altronix
ULXR).
9. Set DIP Switch 5 to OFF to disable Auto
Fallback.
10. Set DIP Switch 6 to ON to prevent fallback
caused hang-ups.
Intercept errors are reported to the
receiver. If the receiver does not
acknowledge a signal sent that was
intercepted by the C900V2 in the
programmed time, the control panel
digital dialer hangs up and retries the
message transmission.
11. Set DIP Switch 9 to ON to enable Anti-
Substitution/Anti-Replay.
12. Set the shorting link on P3 to the H position.
Refer to Figure 13 on page 24 and Table 11 on
page 25 for the proper connection sequence.
®
AL300-
23