Fluke 117 Specifications page 2

Electrician’s multimeter with non-contact voltage

Advertisement

Accuracy specifications
Measurement
Range
DC millivolts
600.0 mV
DC volts
6.000 V
60.00 V
600.0 V
Auto volts
600.0 V
AC millivolts
600.0 mV
1
true-rms
AC volts
1
true-rms
6.000 V
60.00 V
600.0 V
Continuity
600 Ω
Ohms
600.0 Ω
6.000 kΩ
60.00 kΩ
600.0 kΩ
6.000 MΩ
40.00 MΩ
Diode test
2.000 V
Capacitance
1000 nF
10.00 µF
100.0 µF
9999 µF
100 µF to 1000 µF
> 1000 µF
Lo-Z capacitance
1 nF to 500 µF
AC amps true-rms
6.000 A
(45 Hz to 500 Hz)
10.00 A
20 A continuous overload for 30 seconds max.
DC amps
6.000 A
10.00 A
20 A continuous overload for 30 seconds max.
Hz (V or A input)
99.99 Hz
2
999.9 Hz
9.999 kHz
50.00 kHz
Notes:
1
All ac voltage ranges are specified from 1 % to 100 % of range. Because inputs below 1 % of range are not specified,
it is normal for this and other true-rms meters to display non-zero readings when the test leads are disconnected
from a circuit or are shorted together. For volts, crest factor of ≤ 3 at 4000 counts, decreasing linearly to 1.5 at full
scale. AC volts is ac-coupled. Auto-V LoZ, and ac mV are dc-coupled.
2
Frequency is ac coupled, 5 Hz to 50 kHz for ac voltage. Frequency is dc coupled, 45 Hz to 5 kHz for ac current.
2 Fluke Corporation 117 Electrician's Multimeter with Non-Contact Voltage
Resolution
Accuracy ± ([% of reading] + [counts])
0.1 mV
2.0 % + 3
0.001 V
0.01 V
0.1 V
0.1 V
2.0 % + 3 (dc, 45 Hz to 500 Hz)
4.0 % + 3 (500 Hz to 1 kHz)
0.1 mV
1.0 % + 3 (dc, 45 Hz to 500 Hz)
2.0 % + 3 (500 Hz to 1 kHz)
0.001 V
1.0 % + 3 (45 Hz to 500 Hz)
0.01 V
2.0 % + 3 (500 Hz to 1 kHz)
0.1 V
1 Ω
Beeper on < 20 Ω off > 250 Ω; detects
opens or shorts of 500 µs or longer.
0.1Ω
0.9 % + 2
0.001 kΩ
0.01 kΩ
0.9 % + 1
0.1 kΩ
0.001 MΩ
0.01 MΩ
1.5 % + 2
0.001 V
0.9 % + 2
1 nF
0.01 µF
1.9 % + 2
0.1 µF
1 µF
1.9 % + 2
5 % + 20
10 % + 2 typical
0.001 A
1.5 % + 3
0.01 A
0.001 A
1.0 % + 3
0.01 A
0.01 Hz
0.1 Hz
0.1 % + 2
0.001 kHz
0.01 kHz
Ordering
information
Fluke-117
Electrician's
Multimeter with
Non-Contact Voltage
Included
TL75 Test leads, holster, User's
manual and 9V battery (installed).
Fluke. Keeping your world
up and running.
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa (31 40) 2 675 200 or
Fax (31 40) 2 675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2006 Fluke Corporation. All rights reserved.
Printed in U.S.A. 8/2006 2634028 D-EN-N Rev A

Advertisement

loading