Loose wiring may cause the
terminal to overheat or result
WARNING
in unit malfunction. A fire
hazard may also exist.
Therefore, ensure that all
wiring is tightly connected.
When connecting each power wire to the terminal, follow
the instructions on "How to connect wiring to the terminal"
and fasten the wire securely with the fixing screw of the
terminal plate.
How to connect wiring to the terminal
■ ■ For stranded wiring
(1) Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring about 3/8" and
tightly twist the wire ends. (Fig. 4-4)
(2) Using a Phillips head screwdriver, remove the terminal
screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure
terminal.
(4) Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a screwdriver.
(Fig. 4-5)
Stranded wire
Fig. 4-4
Special
Screw
washer
Ring pressure
terminal
Terminal plate
Wire
Wire
Fig. 4-5
27
Ring
pressure
terminal
Screw and
Special washer
Ring
pressure
terminal