Installation Of Rack-Mount Model - NEC Express 5800 User Manual

Hide thumbs Also See for Express 5800:
Table of Contents

Advertisement

Installation of Rack-mount Model

You can mount NEC Express5800/ft series on a rack that conforms to the EIA standards.
IMPORTANT:
NEC Express5800/ft series is a precision instrument. You should ask
maintenance personnel to install it.
To install a rack, contact your sales agent or maintenance personnel.
Do not attempt to install the server.
To avoid the risk of personal injury, users should not attempt to install the
server into the rack assembly. The server should be installed in the rack only by
trained maintenance personnel.
Room that can maintain the following
conditions:
[When operating]
Temperature: 10 to 35ºC*
Humidity: 20 to 80%
Temperature gradient: ±10ºC/hr
Atmospheric pressure: 749 to 1040hpa
[When not operating]
Temperature: 5 to 40ºC*
Humidity: 10 to 80%
Temperature gradient: ±15ºC/hr
Atmospheric pressure: 749 to 1040hpa
* It is recommended to use the server in a room where
temperature can be kept between 15 and 25ºC.
CAUTION
100V - 120 V or 200V - 240 V
parallel bi-polar power outlet
with grounding
Wall outlet within the
reach of supplied power
cord.
Level and reinforced
floor.
Installing Server
Space 40 cm or more on top, 1 m or more
on the front and rear, and 60 cm or more on
the right and left.
3-5

Advertisement

Table of Contents
loading

Table of Contents