FP2−CCU
6.1

Specifications

General Specifications
Item
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity
Vibration resistance
Shock resistance
Noise resistance
Operating condition
Computer Communication Unit Performance Specifications
Item
Interface
Transmission distance
Transmission speed (Baud rate)
Communication method
Synchronous method
Transmission code
Transmission data format
Data transmission order
End terminal code
Computer linking Message
Maximum message length Max. 118 characters/frame
Current consumption
Weight
*1: The value is given as 15 m/49.212 ft. in the specifications, but if used in an environment with a high noise level,
communication may be unstable. Check the conditions using the actual device.
Note
This unit does not support extension header (<). Use the Multi
Communication Unit.
Specifications
0 to 55 °C/32 to 131 °F
–20 to +70 °C/– 4 to + 158°F
30 to 85 % RH (at 25°C non−condensing)
30 to 85 % RH (at 25°C non−condensing)
10 to 55 Hz, 1 cycle/min.: double amplitude 0.75 mm (0.03 in.),
10 min. on 3 axes
Min. 98 m/s
2
, 4 times on 3 axes
1000 V
, 50 ns, 1 μs pulse widths (based on in−house measurements)
p−p
Free of corrosive gases and excessive dust
Specifications
Two RS232C ports
Max. 15 m/49.212 ft
19,200/9,600/4,800 bits/s, selectable using DIP switch
Half duplex
Start−stop synchronous method
ASCII
Stop bit: 1−bit
Parity: Valid (odd)
Character bits: 7−bit/8−bit, selectable using DIP switch
0 bit first in units of characters
CR (0DH)
Header (%) to terminator (CR) Once transmission rights from the
(including "%" and "CR")
60 mA or less (at 5 V DC)
Approx. 120 g/4.233 oz
6.1
*1
host computer are received, com
host computer are received, com-
munication is started. The commu-
nication protocol is MEWTOCOL−
COM.
Specifications