Table 6-13 Technical Data Of Digital Outputs - Siemens Simatic S7-300 Technical Data Manual

Cpu 31xc and cpu 31x
Hide thumbs Also See for Simatic S7-300:
Table of Contents

Advertisement

Technical data
Table 6-13
Technical data of digital outputs
Technical data
Module-specific data
Number of outputs
Of those are fast outputs
Cable length
Unshielded
Shielded
Voltage, currents, potentials
Rated load voltage L+
Polarity reversal protection
Total current of outputs (per group)
Horizontal assembly
up to 104 °F
up to 60 °C
Vertical assembly
up to 104 °F
Electrical isolation
Between channels and the backplane bus
Between the channels
In groups of
Permitted potential difference
Between different circuits
Insulation test voltage
Current consumption
with load voltage L+
Status, interrupts, diagnostics
Status display
Interrupts
Diagnostics functions
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
CPU 312C
CPU 313C
CPU 312C
CPU 313C
6
16
2
4
Caution:
You cannot connect the high-speed outputs of your CPU in parallel.
Max. 600 m
Max. 1000 m
CPU 312C
CPU 313C
24 VDC
No
Max. 2.0 A
Max. 3,0 A
Max. 1,5 A
Max. 2.0 A
Max. 1,5 A
Max. 2.0 A
Yes
No
Yes
8
75 VDC / 60 VAC
500 VDC
Max. 50 mA
Max. 100 mA
CPU 312C
CPU 313C
green LED per channel
no interrupts when operated as standard I/O
For using technological functions, please refer to the
Functions
Manual.
no diagnostics when operated as standard I/O
For using technological functions, please refer to the
Functions
Manual.
Technical data of CPU 31xC
6.6 Technical data of the integrated I/O
CPU 313C-2
CPU 314C-2
CPU 313C-2
CPU 314C-2
16
16
4
4
CPU 313C-2
CPU 314C-2
Max. 3,0 A
Max. 3,0 A
Max. 2.0 A
Max. 2.0 A
Max. 2.0 A
Max. 2.0 A
Yes
Yes
8
8
Max. 100 mA
Max. 100 mA
CPU 313C-2
CPU 314C-2
Technological
Technological
6-49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents