3.3. ZSW Status Word Data

Bit
Valure
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Name
1
Ready To Switch-on
0
Not Ready To Switch-on
1
Ready To Operate
0
Not Ready To Operate
1
Operation Enabled
0
Operation Disabled
1
Fault Present
0
No Fault
1
Coast Stop Not Activated
0
Coast Stop Activated (OFF 2) "Coast Stop (OFF 2)" command is present.
1
Quick Stop Not Activated
0
Quick Stop Activated (OFF 3) "Quick Stop (OFF 3)" command is present
1
Switching On Inhibited
0
Switching On Not Inhibited
1
Warning Present
0
No Warning
Speed Error
1
Within Tolerance Range
Speed Error
0
Out Of Tolerance Range
1
Control Requested
0
No Control Requested
1
f Or n Reached Or Exceeded
0
f Or n Not Reached
----
Device-specification
----
Device-specification
----
Device-specification
----
Device-specification
----
Device-specification
Power supply is switched on
Refer to control word, bit 1.
Drive follows setpoint.
(Refer to control word 1, bit 3)
VF-MB1/S15 tripped.
VF-MB1/S15 is not tripped.
Control word bit1 or 2 is set to 0
or fault trip has been acknowledged.
Drive still operational: Alarm in service parameter: No
acknowledgement.
Alarm not present or alarm has disappeared again
Refer to section 3.3.1.
VF-MB1/S15 is controlled by PROFIBUS master.
VF-MB1/S15 is controlled by another interface.
Actual value ≥ Comparison value (setpoint)
(Reserved.)
(Reserved.)
(Reserved.)
(Reserved.)
(Reserved.)
- 11 -
E6581738
Note
-
-
-
-
-
-
-