Assistance Or Service - Friedrich CP15F10A Installation And Operating Manual

Compact programmable
Table of Contents

Advertisement

Air conditioner power supply cord trips (Reset button
pops out)
Disturbances in your electrical current can trip (Reset
button will pop out) the power supply cord. Press and
release RESET (listen for click; Reset button will latch and
remain in) to resume operation.
Electrical overloading, overheating, cord pinching or
aging can trip (Reset button will pop out) the power
supply cord. After correcting the problem, press and release
RESET (listen for click; Reset button will latch and remain in)
to resume operation.
NOTE: A damaged power supply cord must be replaced with a
new power supply cord obtained from the product manufacturer
and must not be repaired.
Air conditioner seems to run too much
The current air conditioner replaced an older model. The
use of more efficient components may cause the air
conditioner to run longer than an older model, but the total
energy consumption will be less. Newer air conditioners do
not emit the "blast" of cold air you may be accustomed to
from older units, but this is not an indication of lesser cooling
capacity or efficiency. Refer to the efficiency rating (EER) and
capacity rating (in BTU/hr.) marked on the air conditioner.
The air conditioner is in a heavily occupied room, or heat-
producing appliances are in use in the room. Use exhaust
vent fans while cooking or bathing and try not to use heat-
producing appliances during the hottest part of the day. A
higher capacity air conditioner may be required, depending
on the size of the room being cooled.
Air conditioner cycles on and off too much, or does not
cool/heat room in cooling/heating mode
The Mode or Fan control is set to Power Saver (on some
models). Use Power Saver only when you are asleep or away
from home, since the fan does not circulate the room air
continuously. Use Low Cool, Medium Cool or High Cool for
your best comfort.
The air conditioner is not properly sized for your room.
Check the cooling capabilities of your room air conditioner.
Room air conditioners are not designed to cool multiple
rooms.
The filter is dirty or obstructed by debris. Clean the filter.
The inside evaporator and outside condenser coils are
dirty or obstructed by debris. See "Annual Maintenance."
For assistance, service or replacement parts
For service assistance or to locate factory-authorized parts,
call our Customer Service Center at 1-800-541-6645, or your
nearest authorized service center. You also can visit the "Dealer
Locator" at www.friedrich.com to locate your nearest authorized
Friedrich Service Center.

Assistance or Service

15
There is excessive heat or moisture (open container
cooking, showers, etc.) in the room. Use a fan to exhaust
heat or moisture from the room. Try not to use heat-
producing appliances during the hottest part of the day.
The louvers are blocked. Install the air conditioner in a
location where the louvers are free from curtains, blinds,
furniture, etc.
The outside temperature is below 65°F (18°C). Do not try to
operate your air conditioner in the cooling mode when the
outside temperature is below 65°F (18°C).
The temperature of the room you are trying to cool is
extremely hot. Allow extra time for the air conditioner to cool
off a very hot room.
Windows or doors to the outside are open. Close all
windows and doors.
The Vent control is set to OPEN (on some models). Push
the Vent control to CLOSED for maximum cooling and/or
heating.
The temperature set point or Thermostat control is not at
a cool enough setting. Adjust the temperature set point to a
cooler setting by pressing the minus button to reduce the
temperature or adjust the Thermostat control to a cooler
setting by turning the knob clockwise. Turn the Fan control to
Turbo Cool.
The air contitioner in the heating mode has insufficient
BTU/hr for the heating requirements of the room. Do not
use the air conditioner as a primary source of heat.
Temperature on display does not match room
temperature
When the compressor and fan motor turn off during
Power Saver mode, or after you turn off the unit, a lower
temperature reading than the actual room temperature
may be displayed for a short period of time. This lower
temperature reading is caused by the temperature sensor
being located close to the cold evaporator coil. The actual
room temperature will display within a few minutes.
Water drips from cabinet into your house
The air conditioner is not properly leveled. The air
conditioner should slope slightly downward toward the
outside. Level the air conditioner to provide a downward
slope toward the outside to ensure proper drainage. See the
Installation Instructions.
NOTE: Do not drill a hole into the bottom of the metal base
and condensate pan.
For further assistance
If you need further assistance, you can write us at :
Friedrich Air Conditioning Co.
Customer
Service
10001 Reunion Place, Suite 500
San Antonio, TX 78216
Or email: tac@friedrich.com
Please include a daytime phone number in your correspon ence.
d
d

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cp18f30Cp24f30Cp15f10

Table of Contents