Frame Ground Connection - Panasonic KX-TA1232 Installation Manual

Advanced hybrid system
Hide thumbs Also See for KX-TA1232:
Table of Contents

Advertisement

2.2.5 Frame Ground Connection

IMPORTANT
Connect the frame of the main unit to ground.
1.
Loosen the screw.
2.
Insert the grounding wire.
3.
Tighten the screw.
4.
Connect the grounding wire to ground.
In most of the continental United States, the ground provided by the "Third wire ground" at the
commercial power outlet will be satisfactory. However, in a small percentage of cases this
ground may be installed incorrectly. Therefore, the following test procedure should be
performed.
Test Procedure
1.
Obtain a suitable voltmeter and set it for a possible reading of up to 250 V AC.
2.
Connect the meter probes between the two main AC voltage points on the wall outlet. The
reading obtained should be 108 V AC-132 V AC.
3.
Move one of the meter probes to the 3rd prong terminal (GND).
Either the same reading or a reading of 0 V should be obtained.
4.
If a reading of 0 V at one terminal and a reading of 108 V AC-132 V AC at the other terminal
is not obtained, the outlet is not properly grounded.
This condition should be corrected by a qualified electrician (per article 250 of the National
Electrical Code).
5.
If a reading of 0 V at one terminal and a reading of 108 V AC-132 V AC at the other terminal
is obtained, then set the meter to the "OHMS / RX1" scale, place one probe at the GND
Terminal and the other probe at the terminal which gave a reading of 0 V.
A reading of less than 1 ohm should be obtained.
Installation Manual
To ground
To ground
General Installation
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents