Table Pd-17 - Belt Drive Evaporator Fan Performance - Ysc090Ad*H - High Heat - Horizontal Configuration (Si); Table Pd-17A - Belt Drive Evaporator Fan Performance - Ysc090Ad*H - High Heat - Horizontal Configuration - (Ip) - Trane Precedent YSC060-120 User Manual

Packaged gas/electric rooftop units 50hz
Table of Contents

Advertisement

Table PD-17 - Belt Drive Evaporator Fan Performance - YSC090AD*H - High Heat - Horizontal Configuration (SI)

25
50
m
3
/h
RPM
kW
RPM
kW
1.50 Nom kW Standard Motor
& Low Static Drive
4080
713
0.46
764
0.53
4590
790
0.64
837
0.71
5100
869
0.87
910
0.94
5610
949
1.14
985
1.22
6120
1029
1.47
1061
1.55
External Static Pressure (Pascals)
275
300
CFM
RPM
kW
RPM
kW
1.50 Nom kW Std Mtr
& Drive
4080
1101
1.19
1134
1.26
4590
1148
1.43
1180
1.52
5100
1204
1.72
1232
1.81
5610
1264
2.04
1290
2.14
6120
1327
2.43
1352
2.53
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139

Table PD-17a - Belt Drive Evaporator Fan Performance - YSC090AD*H - High Heat - Horizontal Configuration - (IP)

.10
.20
CFM
RPM
BHP
RPM
BHP
2 HP Std Motor & Low Static Drive
2400
713
0.62
764
0.71
2700
790
0.86
837
0.96
3000
869
1.16
910
1.26
3300
949
1.53
985
1.63
3600
1029
1.97
1061
2.07
External Static Pressure (Inches of Water)
1.10
1.20
CFM
RPM
BHP
RPM
BHP
2 HP Std Mtr & Drive
2400
1101
1.59
1134
1.69
2700
1148
1.92
1180
2.04
3000
1204
2.30
1232
2.43
3300
1264
2.74
1290
2.87
3600
1327
3.26
1352
3.39
3 HP Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
30
Performance
Data
External Static Pressure (Pascals)
75
100
RPM
kW
RPM
kW
RPM
1.50 Nom kW Standard Motor & Drive
811
0.61
851
0.67
889
880
0.80
919
0.88
955
950
1.03
989
1.12
1023
1023
1.30
1058
1.40
1092
1096
1.64
1130
1.74
1162
325
350
RPM
kW
RPM
kW
RPM
1.50 Nom kW Standard Motor
& Hi Static Drive
1166
1.34
1197
1.42
1229
1210
1.60
1241
1.69
1269
1260
1.91
1287
2.00
1316
1316
2.25
1342
2.36
1367
1376
2.64
1401
2.75
1425
External Static Pressure (Inches of Water)
.30
.40
RPM
BHP
RPM
BHP
RPM
811
0.81
851
0.89
889
880
1.07
919
1.17
955
950
1.38
989
1.50
1023
1023
1.75
1058
1.88
1092
1096
2.19
1130
2.33
1162
1.30
1.40
RPM
BHP
RPM
BHP
RPM
2 HP Standard Motor
& Hi Static Drive
1166
1.80
1197
1.90
1229
1210
2.15
1241
2.27
1269
1260
2.56
1287
2.69
1316
1316
3.02
1342
3.16
1367
1376
3.54
1401
3.69
1425
125
150
175
kW
RPM
kW
RPM
0.73
926
0.80
962
0.94
989
1.01
1022
1.21
1056
1.28
1086
1.51
1124
1.60
1154
1.85
1193
1.96
1222
2.24 Nom kW Over-Sized
Motor & Hi Static Drive
375
kW
1.50
1.78
2.10
2.46
2.87
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product's Warranty Will Not Be Affected.
.50
.60
BHP
RPM
BHP
RPM
2 HP Standard Motor & Drive
0.97
926
1.07
962
1.26
989
1.36
1022
1.62
1056
1.72
1086
2.02
1124
2.15
1154
2.48
1193
2.63
1222
3 HP Over-Sized Motor & Hi Static Drive
1.50
BHP
2.02
2.39
2.82
3.30
3.85
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product's Warranty Will Not Be Affected.
200
225
kW
RPM
kW
RPM
kW
0.88
997
0.95
1031 1.03
1.09
1054
1.17
1086 1.26
1.36
1116
1.43
1146 1.52
1.68
1182
1.77
1210 1.85
2.06
1250
2.16
1276 2.25
1.50 Nom kW Std Mtr
& Hi Static Drive
.70
.80
.90
BHP
RPM
BHP
RPM BHP
1.17
997
1.28
1031 1.38
1.46
1054
1.57
1086 1.69
1.82
1116
1.92
1146 2.04
2.26
1182
2.37
1210 2.48
2.77
1250
2.89
1276 3.01
2 HP Std Mtr & Hi Static Drive
250
RPM
kW
1067 1.11
1117 1.35
1175 1.62
1237 1.94
1302 2.34
1.00
RPM BHP
1067 1.48
1117 1.80
1175 2.17
1237 2.60
1302 3.13
RT-PRC017-EN

Hide quick links:

Advertisement

Table of Contents
loading