Troubleshooting/FAQs

14.2 Problems when Using Modules of Third-party Manufacturers

14.2
Problems when Using Modules of Third-party Manufacturers
14.2
Problem
Possible causes
I/O addresses are assigned
The PC crashes
twice.
during startup
Hardware interrupts and/or DMA
channels are assigned twice.
Signal frequencies or signal
levels are incorrect.
Connector assignments deviate.
"Reset Configuration" in BIOS
SETUP has not been carried
out.
If the performance of the
external 24 V power supply is
insufficient
14-2
To correct or avoid error
Check your computer configuration:
If the computer configuration corresponds with factory state,
please contact your technical support team.
If the computer configuration has changed, restore the
original factory settings. Remove all third-party modules,
then restart the PC. If the error no longer occurs, the third-
party module was the cause of the fault. Replace this
module with a Siemens module or contact the module
supplier.
Force a "Reset Configuration" using the BIOS setup.
If the PC still crashes, contact your technical support team.
use a larger power supply.
Operating instructions, Release 07/2006, A5E00877780-01
SIMATIC Panel PC 877