Email Notifications Are Not Received From An Hp-Ux Server; Error Led Illuminates Or Flashes; Error During Agent Installation; Event Notification Messages Do Not Appear On Console Screen - HP UPS User Manual

Table of Contents

Advertisement

Install an SSL certificate that Internet Explorer recognizes.
-or-
Click Continue to this website (not recommended) to ignore the security warning.
Email notifications are not received from an HP-UX
server
Action: Add the IP address of the email server to the host file of the computer running the UPS Power
Protection Agent.

Error LED illuminates or flashes

Action: Press the Reset button on the management module front panel. If the problem persists, contact an
authorized service provider.
The following table lists the error conditions associated with the management module LED.
Test
1
2
3
4
5
6

Error during agent installation

Symptom: An error occurs while installing the agent on servers with Red Hat 5.0.
Possible cause: Security enhanced Linux is enabled.
Action: Run the following commands:
#chcon –t textrel_shlib_t
1.
/etc/init.d# ./DevMan setup
2.
#chcon –t textrel_shlib_t
3.
Event notification messages do not appear on
console screen
Action: If you are using SLES 9, upgrade the KDE or use a different desktop, such as GNOME.
LED flash error code
Permanently on
2 flashes
3 flashes
4 flashes
5 flashes
6 flashes
Description
DRAM failure
DMA Mem to Mem error
IRQ error
Ethernet error
Serial loop back error
RTC error