Fieldbus Slave Modules - Hitachi EH-150 Series PLC Engineering Manualline

Eh-150 series plc
Table of Contents

Advertisement

Engineering Guideline

Fieldbus Slave Modules

Item
Fieldbus system
General
Type
Function
Max. number of base-racks
Max. number of modules
Node address range
Max. number of I/O's (with
64 point I/O modules
Max. input and output data
In data update cycle time
9.6 kbps
19.2 kbps
45.45 kbps
93.75 kbps
125 kbps
Max. segment
187.5 kbps
lenght (at data
250 kbps
transfer rate).
500 kbps
1500 kbps
3 Mbps
6 Mbps
12 Mbps
Internal current consumption (5V)
I/O assignment
External connection
External wiring
Self diagnosis
File for configuration
Configurator software
EH-IOCP
Profibus-DP
Profibus-DP slave module for use with
standard I/O modules of EH-150 series
2 (2nd rack connected via EH-IOC)
16
1 - 99
1024
208 words
5ms
1200m
1200m
1200m
1200m
-
1000m
-
400m
200m
100m
100m
100m
Approx. 600mA
fixed at CPU-Slot
9 pin D-sub, female
Double shielded twisted pair cables
according to Profibus specification
System ROM/RAM check,
watch-dog timer check
GSD-file, File name:Hita049d.gsd.
This file can either be downloaded
from the web (www.hitachi-
ds.com/sub/info/updates) or received
directly from Hitachi Europe
Profibus configurator software,
Order-Number: PBDP-M-CONF
8
EH-150 Series PLC
EH-IOCD
DeviceNet
DeviceNet slave module for use with
standard I/O modules of EH-150 series
2 (2nd rack connected via EH-IOC)
16
1 - 63
1024
208 words
5ms
-
-
-
-
500m
-
250m
100m
-
-
-
-
Approx. 600mA
fixed at CPU-Slot
5-pole DeviceNet connector
TM
DeviceNet
dedicated cable
System ROM/RAM check,
watch-dog timer check
EDS-file, File name: Absdev.eds.
This file can either be downloaded
from the web (www.hitachi-
ds.com/sub/info/updates) or received
directly from Hitachi Europe
DeviceNet configurator RSNetworx
and dedicated interface adapter

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents