Installation Instructions; Venting Methods - Whirlpool UXD8630DYS0 Use & Care Manual

30" and 36" retractable (pop-up) downdraft vent system
Table of Contents

Advertisement

Available languages

Available languages

INSTALLATION INSTRUCTIONS
Determine which venting method is best for your application.
Island
Location--Vent
System
Installed
Under a Concrete
Vent system can terminate either through the wall or floor.
Slab Using
PVC Sewer
Pipe
Island Location
Front (Standard)-Mounted
Blower Motor
Rear-Mounted
Blower Motor
m
&
m
L=========J=
. _ ....................................................
i_,_-' A
Front (Standard) Mounted Blower Motor
B
K
..............................................
E
_bi,_
..............
G
........
H
/
Rear Mounted Blower Motor
A. Down vent
NOTE: For island locations, a front- or rear-mounted
blower
motor can also be mounted for right or left venting if needed for
your application.
Most island applications
would still require the
venting to be directed down through the floor.
Built-In Cabinet Locations
A
S
K
B
A. Down vent
B. Left vent
C. Right vent
C
A. Wall cap
B. 6" (15.2 cm) round metal vent
C. 16" (40.6 cm) maximum
D. 6" (15.2 cm) round PVC sewer pipe
E. 6" (15.2 cm) round metal vent transition with damper (supplied)
F. 6" (15.2 cm) round PVC coupling
G. Concrete slab
H. 6" (15.2 cm) round PVC sewer pipe
I. 6" (15.2 cm) round 90 ° PVC sewer pipe elbow
J. Tightly pack gravel or sand completely
around pipe.
K. 6" (15.2 cm) round 90 ° PVC sewer pipe elbow
L. 6" (15.2 cm) round PVC coupling
M. 12" (30.5 cm) minimum
Calculating
Vent System
Length
31¼ '' x 10" (8.3 x 25.4 cm) rectangular vent is required from the
blower motor box. It can be transitioned
to 6" (15.2 cm) round
vent if needed.
Maximum
Length of Vent System
Vent
Length
6" (15.2 cm) round
35 ft (8.9 m)
31/4 '' x 10" (8.3 cm x 25.4 cm)
35 ft (8.9 m)
8

Advertisement

Table of Contents
loading

Table of Contents