Troubleshooting - Honeywell VisionPRO 8000 Owner's Manual

Visionpro 8000 series touchscreen programmable thermostat
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

VisionPRO
TM 8000
Touchscreen
Programmable
Thermostat
TROUBLESHOOTING (TABLE14)
Table
14. Troubleshooting.
Symptom
Possible
Cause
Display
does
not come
on.
Thermostat
is not being powered.
Temperature settings do not
change.
Heating
or cooling
does
not
come on.
Thermostat is calling for Heat
(Heat on) or Cool (Cool on) but
no heating or cooling is
running.
Heat does not turn on (Heat
On is solid in the display).
The upper or lower temperature limits
were reached.
The keypad
is fully locked.
Thermostat
minimum
off-time
is
activated.
System
selection
is not set to Heat or
Cool.
System
type Selection
is incorrect.
Heating or cooling equipment is not
operating.
Heating
equipment
failure.
Loose
or broken
wire connection
between
thermostat
and heating
equipment.
Cooling
equipment
failure.
Loose
or broken
wire connection
between
thermostat
and cooling
equipment.
Cooling
does not turn on (Cool
On is solid in the display).
Fan does
not turn on in a call
Fan Control
in Heating
is set to Gas or
for heat
(electric
furnace).
Oil Furnace
(Setting
0180).
Action
Check for 24 Vac between
C and Rc.
Check
that AAA batteries
are installed
correctly
and are good.
Check temperature
setpoints.
Check
Installer
Setup
Numbers
0600
and
0610;
modify
as needed.
Check
Installer
Setup
Number
0670 to
change
keypad
locked
options.
Wait up to five minutes
for the system
to
respond.
Set system
Selection
to correct
position.
Check
Installer
Setup
Number
0170 and
make sure correct
System
type is chosen.
Check wiring.
Check
Installer
Setup
Number
0170
and
make sure correct
system
type is chosen.
Verify operation
of equipment
in System
Test
mode.
Check for 24 Vac at the equipment
on the
secondary
side of the transformer
between
)ower
and common.
If voltage
is not present,
check the heating
equipment
to find the cause
of the problem.
Check for 24 Vac between
the heat terminal
(W) and transformer
common.
If 24 Vac is
)resent,
the thermostat
is functional.
Check
the heating
equipment
to find the cause of the
)roblem.
Check for 24 Vac between
the heat terminal
(W) and transformer
common.
If voltage
is not
)resent,
check wire connection
(loose or
broken)
between
the thermostat
and the
heating
equipment.
Check for 24 Vac at the equipment
on the
secondary
side of the transformer
between
)ower
and common.
If voltage
is not present,
check the cooling
equipment
to find the cause
of the problem.
Check for 24 Vac between
the cool terminal
(Y) and transformer
common.
If 24 Vac is
)resent,
the thermostat
is functional.
Check
the cooling
equipment
to find the cause of the
)roblem.
Check for 24 Vac between
the cool terminal
(Y) and transformer
common.
If voltage
is not
)resent,
check the wire connection
(loose
or
broken)
between
the thermostat
and the
cooling
equipment.
Set Fan Control
in Heating
to Electric
Furnace
(Setting
0180).
68-0280
38