Dell PowerEdge UPS 500T Installation And Configuration Manual page 115

Dell ups management software installation and configuration user's guide
Hide thumbs Also See for PowerEdge UPS 500T:
Table of Contents

Advertisement

4 Enter the shutdown commands (see Figure 116).
Example:
shutsys -ip 172.18.127.47 -e true
shutbackup -ip 172.18.127.47 -e true -m 1:00
shutfile -e true -f shutdown -m 2
listshut -ip 172.18.127.47
NOTE:
See "Dell CUI Commands List" on page 132 for a description of all Dell CUI commands.
NOTE:
Each guest operating system requires a minimum of 30 seconds to run the command file before shutdown.
The -m 1 option in the shutfile command in the example below sets one minute as the total time allowed to run the
command file before shutdown, which allows sufficient time for two guest operating systems.
Example: shutfile -e true -f shutdown.sh -m 1
The host and guest operating system shut down orderly and gracefully after the battery discharges for
one minute.
Figure 116. Shutdown Parameters
NOTE:
The VMware ESX and ESXi Server Scripts are from William Lam, VMware vExpert. 
http://communities.vmware.com/docs/DOC-9531
Thanks to William Lam (@lamw on Twitter and VMTN) for use of the Scripts.
Installation on a VMware ESX Server
115