If the test message is not received at the E-mail address, check the E-mail server settings.
SNMP notification
To receive VLS notification alerts on a management console(s), you must edit the SNMP settings to specify
the management console(s) you want to receive VLS SNMP traps.
Editing the SNMP settings
NOTE:
To display VLS notification alerts on a management console, the management console must be running
HP Systems Insight Manager, and be configured to receive SNMP traps from the VLS.
To add a management console(s) to the SNMP alert distribution list:
1.
Log in to Command View VLS as the administrator. See
from Command View
2.
Click the Notifications tab.
The Notifications window displays
3.
Click Edit SNMP Setting in the task bar.
The Edit SNMP Settings window opens
Figure 69 Edit SNMP Settings window
4.
To add management consoles:
a. Enter the host name of a management console that you want to receive VLS SNMP traps in
the Hostname box.
b. Enter the string name that is passed with the set to get commands from the management console
in the Community String box.
This value is typically set to Public.
c.
Select the appropriate trap version for the management application that will receive the SNMP
traps in the Trap Version box.
Select 1 for the trap version if your management application is HP Systems Insight Manager.
d. Click Add.
e.
To add another management console, repeat these steps.