To Change To 115 Volts; Dial Type Voltage Selector; Connection Procedure; Wiring Connections - Craftsman 390.2532 Owner's Manual

Multi-stage jet pump
Table of Contents

Advertisement

ELECTRICAL
To change
to
I 15 volts:
1. Make sure power is off.
2. Pull the ping toward
you.
3. Move and attach
the plug at the 115 volt position.
The plug vfdl now cover 2 metal tabs.
4. Reinstall
the Motor
end cover
5. Go to Wiring
Connections
below.
Dial Type Voltage
Selector
Connections
Figure
16 - Voltage
Set To 230 Volts, Dial Type
ranty. The supply voltage
must be within
+10% of the
motor
nameplate
voltage.
NOTICE:
Dual-voltage
motors
are factory
wired
for
230 volts. If necessary,
reconnect
the motor
for 115
volts, as shown.
Do not alter the wiring
in single volt-
age motors.
Install, ground,
wire, and maintain
your pump
in com-
pliance
with the National
Electrical
Code (NEC) or the
Canadian
Electrical
Code
(CEC),
as applicable,
and
with all local codes and ordinances
that apply. Consult
your local building
inspector
for code information.
Motor wires connect here.
pply wires connect here.
230 Volt: Connect 2 hot wires (black and red
here and cap the wh te neutra wire. t does
not matter which wire goes to which screw.
115 Volt: Connect one hot wire (black or red)
to one ctfthese screws (i1doesn't matter
which one). Connect the white (neutral) wire
to the other screw, Cap any remaining
black or red wires.
prevent strain
on the terminal screws.
- Connect the green (or bare copper) ground wire
to the green ground screw.
31870398
Figure
17 - Pressure Switch Wiring
To change
to
I 15 volts:
1. Make sure power
is off.
2. Turn the dial counter-clockwise
until 115 shows
in
the dial window.
3. Reinstall
the Motor
end cover
4. Go to Wiring Connections
below.
[_,WARNING]Hazardous
voltage.
Can
shock,
burn,
or kill. Connect
ground
wire
before
connecting
power
supply
wires.
Use the wire
size (including
the ground
wire)
specified
in the wiring
chart.
If
possible,
connect
the pump
to a separate
branch
cir-
cuit with no other
appliances
on it.
IAwARNING] Explosion
hazard.
Do not
ground
to
a gas
supply
fine.
Wiring
Connections
Fire hazard.
Incorrect
voltage
can cause
a fire or seriously
damage
the motor
and voids the war-
Connection
Procedure
1. Connect
the ground
wire first as shown
in Figure 14.
The ground
wire must be a solid copper
wire at least
as large as the power
supply wires.
2. There must be a solid metal connection
between
the
pressure
switch
and the motor
for motor
grounding
protection.
If the pressure
switch
is not connected
to the motor, connect
the green ground
screw in the
switch
to the green ground
screw under
the motor
end cover. Use a solid copper
wire at least as large
as the power
supply wires.
3. Connect
the ground
wire to a grounded
lead in a ser-
vice panel, to a metal underground
water
pipe, to a
metal wen casing at least ten feet (3M) long, or to a
ground
electrode
provided
by the power
company
or the hydro authority.
4. Connect
the power
supply
wires
to the pressure
switch
as shown
in Figure 17.
WIRING
CHART
- Recommended
Wire
and Fuse Sizes
MOTOR
MAX. LOAD
lip
VOLTS
AMPS
1
115/230
19.2/9.6
BRANCH FUSE* I
DISTANCE IN FEET FROM MOTOR TO METER
RATING (AMPS)
0 to 50
51 to 100
101 to 200
201 to 300
25/15
10/14
10/12
8/10
6/10
(*)Time delay fuse or circuit breakers are recommended in any motor circuit.