Setting Ip Addresses For Remote Communication; Hmi Ip Address; Cpu Ip Address - GE Entellisys DEH-230 System Administrator Manual

Low voltage switchgear
Table of Contents

Advertisement

6.1 Setting IP addresses for remote communication

6.1.1 HMI IP address

6

6.1.2 CPU IP address

22
Configuring the switchgear for remote communications
Step 8: Install Remote HMIs.
See
Installing and configuring remote HMI software on page
Step 9: Verify communication between Remote HMI and CPUs.
See Chapter 5.2. [dk: there is no section 5.2?]
To change the HMI IP address
1. For the HMI touchscreen computer, login to the Operating System as Administrator. See
Administrator access to the operating system on page 61
2. Open the Control Panel, and then open the Network Connections dialog box.
3. Double-click the Local Area Connection 1.
4. In the TCP/IP Properties tab, set the new Local HMI IP address. Set the subnet mask to a
value compatible with the segment on which it resides.
By default the subnet mask is set to 255.255.255.0. The default touchscreen HMI IP address is
192.168.1.1 as delivered. The default IP address for each additional touchscreen HMI is
incremented by 1 in the right-most address.
To change the CPU IP addresses
1. On the Main Menu, click User Settings.
2. Click HMI Preferences.
3. Click Communication.
4. Select either CPU A or CPU B by clicking the appropriate button.
5. Enter the new IP address. The IP address format is X.X.X.X where X is from 0 to 255.
25.
for details.