Fujitsu PRIMECENTER M1 19-inch Rack User Manual page 79

Rack system for primergy, primequest, bs2000, storage
Table of Contents

Advertisement

7.3.2.2
Installation options for 700 mm wide symmetrical racks
Rack height
Installation direction vertically
conditionally possible 1
42 HU
conditionally possible 1
24 HU
Table 6: Installation options for asymmetrical racks
1
Installation is only possible on the rear side. Cable routing is restricted. Installation of cable
arms at the same height is not possible.
Performing the task
Ê Install the PDU brackets as described on
Figure 47: 10-way socket strip "Blade PDU" mounted in a 700 mm wide symmetrical rack
Ê Screw the socket strip with 2 screws onto the PDU brackets.
I
Installation is possible on both sides.
Power Distribution
Installation direction horizontally
Max. 2x with PDU kit 3 HU
Max. 2x with PDU kit 3 HU
page
69.
79