Mrlds Dimensions; Mrlds Analog Version (809-100X); Network Layout; Mrlds Wiring - Emerson MRLDS Operation Manual

Modular refrigerant leak detection sensor (mrlds)
Table of Contents

Advertisement

Figure 2-2
- Attaching and Removing Cover
2.2

MRLDS Dimensions

Figure 2-3
- MRLDS Mounting Dimensions
MRLDS Dimensions
3
MRLDS Analog
Version (809-100x)
3.1

Network Layout

E2
Figure 3-1
- Analog MRLDS Network Layout Example
3.2

MRLDS Wiring

For analog MRLDS units, connect to a MultiFlex
board via the analog input (use Belden 8761 cable).
Analog MRLDS
to MultiFlex
ANALOG MRLDS -
INSIDE LOWER PORTION
OF BASE
TO 24VAC, 10VA
CLASS 2 POWER
SUPPLY
BELDEN
8761
EARTH SHIELD
NEAR THE MULTIFLEX
BOARD.
DO NOT
THE SHIELD TO THE 0V INPUT
ON THE MULTIFLEX BOARD.
Wire MultiFlex SIG to MRLDS OUT(V).
Wire MultiFlex 0V to MRLDS Ground (
Figure 3-2
- Analog MRLDS Wiring

MRLDS Analog Version (809-100x)

I/O Net
MultiFlex Board
MRLDS Units
MULTIFLEX BOARD -
LOWER RIGHT CORNER
1
2
3
4
5
6
7
8
0V
SIG
0V
SIG
0V
SIG
0V
SIG
INPUT 13
INPUT 14
INPUT 15
INPUT 16
A transformer must
never
be shared
between MRLDS
and the MultiFlex
BELDEN
board. A
separate
8761
transformer
must
be used.
If a transformer is
shared between
MRLDS units,
CONNECT
the "ACN" of
each MRLDS
must be wired
to the same
).
phase of the
transformer.