SJ300 intelligent output terminal default setting
3.4 Expansion cards
(1) J-RY (Relay output PCB)
Please use L300PTM (standard control signal) terminal block.
Refer to Chart 9 for its specifications.
J-RY(J300)
Terminal
Terminal specifications
symbol
AC250V, 2.5A (R load),
RYA1 RYA0
0.2A (I load)
DC30V, 3A (R load),
RYB1 RYB0
0.7A (I load)
Minimum load
RYC1 RYC0
AC100V, 10mA,
DC5V, 100mA
(2) J-R0T0 (Control power supply PCB)
The SJ300 has R0T0 terminals as standard.
When supplying the R0T0 terminals with power externally, remove J51 jumper beforehand.
(3) J-FB (Feedback PCB)
Please use SJ-FB.
The SJ-FB does not have the analog monitor (MA1 and MA2) which the J-FB has.
When this function is required, please use the analog monitor provided on the SJ300 (AM and
AMI).
C031
C032
C033
C034
C035
Chart 8
Chart 9
Relay output function comparison chart
NO
NC
NO
NC
NO
NC
NO
NC
NO
NC
L300PTM(SJ300)
Terminal
Terminal specifications
symbol
AC250V, 5A (R load),
11A
11C
1A (I load)
DC30V, 5A (R load),
12A
12C
1A (I load)
Minimum load
-
-
AC100V, 10mA,
DC5V, 100mA
14/24