Typical Addressable Facp Connection To 411Udac - Fire-Lite 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual

Fire alarm communicator
Table of Contents

Advertisement

Input Channels

Typical Addressable FACP Connection to 411UDAC

FIGURE 2-7:
Note: The addressable monitor module
input, which is being used to monitor the
411UDAC Relay Output programmed for
DACT Trouble (requires optional 411RK
Relay Kit), must be programmed as
'DACT Trouble' at the FACP. The
411UDAC must be programmed as a
Slave Communicator (programming
address 64 set to '2')
End-of-Line Resistor
2.2K
supplied with
EOL
Monitor Module
Addressable FACP
(must be UL-listed for
Central Station Service
and Remote Signaling
Service)
Program the 411UDAC as follows:
Channel 1 - Normally Open Contact Device (alarm)
Channel 2 - Host Panel Trouble
Channel 3 - Supervisory
411UDAC Relay 2 Output (DACT Trouble)
Channel 2/Zone 2
Channel 1/Zone 1
Channel 3/Zone 3
2.2K EOL Channel 4
411UDAC
Supervisory Relay
411UDAC
Document #51073
Alarm Relay
Trouble Relay
UL listed
2.2K EOLs
P/N 27070
Rev. D 12/09/2008
P/N 51073:D
*If the SLC device does not
match the one in this figure,
refer to the SLC manual wiring
conversion charts for legacy
and newer versions of the
modules.
Monitor Circuit Input
Monitor
Module*
SLC Loop
25