Pr.161 Frequency setting/key lock operation selection
You can use the setting dial of the operation panel (FR-DU07)
like a potentiometer to perform operation.
The key operation of the operation panel can be disabled.
Pr.161 Setting
0 (initial value)
Setting dial frequency setting mode
1
Setting dial potentiometer mode
10
Setting dial frequency setting mode
11
Setting dial potentiometer mode
Refer to the section about Pr. 57 and
Pr.
162 to 165
other relevant parameters.
Refer to the section about Pr. 150 and
Pr.
166, 167
other relevant parameters.
Parameter for manufacturer setting. Do not set.
Pr.
168, 169
Refer to the section about Pr. 52 and
Pr.
170, 171
other relevant parameters.
Refer to the section about Pr. 160 and
Pr.
172 to 174
other relevant parameters.
Function assignment of
Pr.
178 to 189
input terminal
Pr.178 STF terminal function selection
Pr.180 RL terminal function selection
Pr.182 RH terminal function selection
Pr.184 AU terminal function selection
Pr.186 CS terminal function selection
Pr.188 STOP terminal function selection Pr.189 RES terminal function selection
Use these parameters to select/change the input terminal functions.
Pr.178 to
Signal
Pr.189
Name
Setting
Pr.59 =0
0
RL
(initial value)
Pr.59 =1, 2
Pr.59 =0
1
RM
(initial value)
Pr.59 =1, 2
Pr.59 =0
2
RH
(initial value)
Pr.59 =1, 2
3
RT
Second function selection
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
Selection of automatic restart after instantaneous
6
CS
power failure, flying start
7
OH
External thermal relay input
15 speed selection
8
REX
(combination with three speeds RL, RM, RH)
Inverter operation enable signal
10
X10
(FR-HC, FR-CV connection)
FR-HC connection, instantaneous power failure
11
X11
detection
12
X12
PU operation external interlock
14
X14
PID control valid terminal
16
X16
PU-external operation switchover
24
MRS
Output stop
25
STOP
Start self-holding selection
Forward rotation command
60
STF
(assigned to STF terminal (Pr. 178) only)
Reverse rotation command
61
STR
(assigned to STR terminal (Pr. 179) only)
62
RES
Inverter reset
PTC thermistor input
63
PTC
(assigned to AU terminal (Pr. 184) only)
64
X64
PID forward/reverse action switchover
65
X65
NET/PU operation switchover
66
X66
External/NET operation switchover
67
X67
Command source switchover
9999
No function
*1
When Pr. 59 Remote function selection = "1" or "2", the functions of the RL,
RM and RH signals are changed as given in the table.
*2
The OH signal turns on when the relay contact "opens".
41
indicates simple mode parameters and
Pr.
Description
Key lock mode
invalid
Key lock mode
valid
Pr.179 STR terminal function selection
Pr.181 RM terminal function selection
Pr.183 RT terminal function selection
Pr.185 JOG terminal function selection
Pr.187 MRS terminal function selection
Function
Low speed operation command
Remote setting (setting clear)
*1
Middle speed operation
command
Remote setting (deceleration)
*1
High speed operation command
Remote setting (acceleration)
*1
*2
indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
Terminal assignment of
Pr.
190 to 196
output terminal
Pr.190 RUN terminal function selection Pr.191 SU terminal function selection
Pr.192 IPF terminal function selection
Pr.194 FU terminal function selection
Pr.196 ABC2 terminal function selection
You can change the functions of the open collector output
terminal and relay output terminal.
Pr.190 to Pr.196
Setting
Signal
Name
Positive
Negative
logic
logic
0
100
RUN
1
101
SU
2
102
IPF
3
103
OL
4
104
FU
5
105
FU2
5
105
FU2
7
107
RBP
10
110
PU
11
111
RY
12
112
Y12
13
113
Y13
14
114
FDN
15
115
FUP
16
116
RL
17
MC1
18
MC2
19
MC3
25
125
FAN
26
126
FIN
45
145
RUN3
46
146
Y46
47
147
PID
64
164
Y64
70
170
SLEEP
90
190
Y90
91
191
Y91
92
192
Y92
93
193
Y93
94
194
ALM2
95
195
Y95
96
196
REM
98
198
LF
99
199
ALM
9999
* Setting can be made for the 75K or more.
Pr.
Refer to the section about Pr.4 to Pr.6
232 to 239
Refer to the section about Pr. 72 and other
Pr.
240
relevant parameters.
Pr.
Refer to the section about Pr. 125, Pr.126
241
Refer to the section about Pr. 73 and
Pr.
242, 243
other relevant parameters.
Pr.193 OL terminal function selection
Pr.195 ABC1 terminal function selection
Function
Inverter running
Up to frequency
Instantaneous power failure/
undervoltage
Overload alarm
Output frequency detection
Second output frequency
detection
Second output frequency
detection
Regenerative brake prealarm *
PU operation mode
Inverter operation ready
Output current detection
Zero current detection
PID lower limit
PID upper limit
PID forward/reverse rotation
output
Commercial power-supply
switchover MC1
Commercial power-supply
switchover MC2
Commercial power-supply
switchover MC3
Fan fault output
Heatsink overheat pre-alarm
During inverter running and start
command is on
During deceleration at
occurrence of power failure
(retained until release)
During PID control activated
During retry
During PID output suspension
Life alarm
Alarm output 3 (power-off signal)
Energy saving average value
updated timing
Current average monitor signal
Alarm output 2
Maintenance timer signal
Remote output
Minor fault output
Alarm output
No function